| 2017-11-09 17:02:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THE IS NO NOTE INDICATING COMPLAINCE WITH ANY LIFE |
| | SAFETY CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | |
| | |
| | 2) SHEET 130 A 1.2 - THERE IN NO INDICATION OF ANY |
| | EXISTING OR PROPOSED BUILDING INFORMATION. I.E. TYPE OF |
| | CONSTRUCTION, FIRE SPRINKLER, FIRE ALARM, INTEIOR |
| | FINISHES, ETC. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 3) SHEET 110 A 1.0 - THE DOOR SCHEDULE DOES NOT |
| | INDICATE ANY INFORMATION REGARDING EXISITNG DOORS AND |
| | HARDWARE.. |
| | |
| | PLEASE PROVIDE DOOR DETAILS, INCLUDING, TYPE, SIZE, |
| | LOCKS, LATCHES, HARDWARE, ETC. THAT MEET THE |
| | REQUIRMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | |
| | |
| | 4) SHEET 130 A 1.2 - A KITCHEN IS INDICATED. THERE IS |
| | NO INFORMATION REGARDING COMPLIANCE WITH NFPA 96, |
| | STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF |
| | COMMERCIAL COOKING OPERATIONS, 2011 EDITION, EITHER |
| | EXISITNG OR PROPOSED. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANT EXISITNG |
| | OR PROPOSED SHOP DRAWINGS UNDER SEPARATE PERMIT. |
| | |
| | |
| | |
| | 5) SHEET 120 A 1.1 - A PIZZA OVEN IS INDICATED. THERE |
| | ARE NO SPECIFICATION SHEETS OF PROPTECTION PER NFPA 96 |
| | OR INSTALLTION & VENTILATION REQUIRERMENTS. |
| | |
| | PLEASE PROVIDE MANUFACTURES DETAIL SHEETS INCLUDING |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | |
| | |
| | 6) SHEET 130 A 1.2 - THERE IS ONLY ONE EXIT FROM THE |
| | MAIN AREA AND TWO ARE REQUIRED. THE EXIT FROM THE MAIN |
| | AREA CAN NOT PASS THRU THE KITCHEN AREA. |
| | |
| | PER NFPA 101, CHAPTER 12, NEW ASSEMBLY OCCUPANCIES, |
| | |
| | 12.2 MEANS OF EGRESS REQUIREMENTS. |
| | 12.2.1 GENERAL. ALL MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH CHAPTER 7 AND THIS CHAPTER. |
| | |
| | 12.2.4* NUMBER OF MEANS OF EGRESS. |
| | 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH SECTION 7.4, OTHER THAN EXITS FOR |
| | FENCED OUTDOOR ASSEMBLY OCCUPANCIES IN ACCORDANCE WITH |
| | 12.2.4.4. |
| | |
| | 7.4* NUMBER OF MEANS OF EGRESS. |
| | 7.4.1 GENERAL. |
| | 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY, |
| | MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS |
| | THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS: |
| | (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE |
| | PERMITTED IN CHAPTERS 11 THROUGH 43. |
| | (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A |
| | MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL |
| | LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET. |
| | |
| | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND |
| | 7.2.1.5. |
| | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH |
| | KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS |
| | 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR |
| | SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO |
| | LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS |
| | PERMITTED FOR THE OCCUPANCY BY CHAPTER |
| | 18, 19, 22, OR 23. |
| | |
| | PLEASE CORRECT OR PROVIDE FFPC REFERENCE FOR THE |
| | EXCEPTION. |
| | |
| | |
| | |
| | 7) SHEE 120 A 1.1 - THERE ARE NO INDICATIONS OF FIRE |
| | SPRINKLER OR FIRE ALARM WORK. ALL WORK ON ANY EXISTING |
| | FIRE SPRINKLER OR FIRE ALARM SYSTEM SHALL BE DONE UNDER |
| | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| | CONTRACTORS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | 8) SHEET 100 A 0.0 - THERE IS INDICATIONS OF OCCUPANCY |
| | LOADS CALCULATION. THERE IS NO INDICATIONS OF THE |
| | OCCUPANCY LOAD FOR THE BAR COUNTER AREA. |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |