| 2017-11-27 15:18:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR 800 AMP SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 2. PROVIDE AUTOMATIC LIGHTING CONTROL FOR EXTERIOR |
| | LIGHTING AND SIGN CIRCUIT. ENERGY CODE STATES: LIGHTING |
| | NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND |
| | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE |
| | 405.2.4 |
| | 3. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. FBC CE 405.5 |
| | 5. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER NEC 210.62. |
| | 6. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS |
| | REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 7. PROVIDE DETAILS OF SHUTDOWN FOR ANY EQUIPMENT AND/OR |
| | RECEPTACLE OUTLETS LOCATED UNDER HOOD. NFPA 96, SECTION |
| | 10.4.1, FBC 107.2.1 |
| | 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| | CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS |
| | ADEQUATE. NEC 110.10 |
| | 9. CIRCUIT OR RECEPTACLE OUTLET FOR WATER FOUNTAIN |
| | REQUIRES GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | GENERATORS, COMMERCIAL HOOD SYSTEMS, SIGNS, SITE |
| | LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT |
| | INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A |
| | BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND |
| | DATA SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE |
| | SYSTEMS PRESENT. FBC 105.1, 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |