2017-11-27 15:18:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR 800 AMP SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 2. PROVIDE AUTOMATIC LIGHTING CONTROL FOR EXTERIOR
 LIGHTING AND SIGN CIRCUIT. ENERGY CODE STATES: LIGHTING
 NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE
 405.2.4
 3. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
 5. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER NEC 210.62.
 6. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS
 REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 7. PROVIDE DETAILS OF SHUTDOWN FOR ANY EQUIPMENT AND/OR
 RECEPTACLE OUTLETS LOCATED UNDER HOOD. NFPA 96, SECTION
 10.4.1, FBC 107.2.1
 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10
 9. CIRCUIT OR RECEPTACLE OUTLET FOR WATER FOUNTAIN
 REQUIRES GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 GENERATORS, COMMERCIAL HOOD SYSTEMS, SIGNS, SITE
 LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT
 INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A
 BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND
 DATA SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE
 SYSTEMS PRESENT. FBC 105.1, 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  