| Plan Review Notes For Permit 17110229 |
| Permit Number |
17110229 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-08 14:45:16 | 11/8/17 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) PLEASE EXPLAIN IS THIS A LIKE FOR LIKE REPLACEMENT | | | AND ARE ANY DRAINS BEING ADDED OR DELETED FROM THE | | | EXISTING SYSTEM OR CHANGING OF SIZE OF ANY DRAINS. FBC | | | 107.2.1 | | | | | | 2) PLEASE EXPLAIN HOW YOU PLAN ON LEAK CHECKING IF YOU | | | DO NOT PLAN ON ON CUTTING DRYWALL CEILING OPEN FROM | | | BELOW AND HOW THE INSPECTOR IS INSPECT WORK HE IS | | | UNABLE TO SEE. FPC 312.1- RUNNING TEST OK | | | | | | 3) PROVIDE MANUFACTURE INSTALLATION MANUAL AND ROOF | | | DRAIN SPEC (2-COPIES OF EACH) | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|