| 2018-09-18 11:06:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: NEW REVIEW BASED ON DESIGN |
| | PROFESSIONAL CHANGE. DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION TO JUSTIFY SERVICE |
| | SIZE. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT. |
| | NEC 220 |
| | 2. BASED ON LOADS PROVIDED, SERVICE IS NOT OF |
| | SUFFICIENT SIZE FOR THE LOAD. PROVIDE CORRECTION. NEC |
| | 215.2, 215.3, 408.30, 408.36 |
| | 3. BASED ON LOADS PROVIDED, FEEDERS TO FPL ARE NOT |
| | SIZED PROPERLY. PROVIDE CORRECTION. NEC 310.15(B)(16) |
| | 4. PROVIDE CALCULATION FOR WIRE SIZE TO METERS/ METER |
| | BANKS. NEC 220, 215.2, 215.3, 240.21 |
| | 5. PROVIDE METHOD OF TAPPING WIRES TO EACH METER. AS |
| | SHOWN ON PLAN, THE WIRES WOULD GO TO INDIVIDUAL METERS. |
| | HOW WOULD THIS BE ACCOMPLISHED? IF A TAP IS TO BE USED, |
| | TAP RULES DICTATE THAT THE TAPS MUST TERMINTATE IN A |
| | SINGLE BREAKER OR SET OF FUSES. PROVIDE COMPLIANCE. NEC |
| | 240.21(B)(5); WPB FBC 107.2.1 |
| | 6. SHEET E-1 SHOWS UNIT TYPES A, B, AND C. SHEET E-3 |
| | SHOWS UNIT TYPES A AND B. ATTEMPTED LOAD CALCULATION |
| | SHOWS 3 TYPES OF UNITS. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. WPB FBC 107.2.1 |
| | 7. PROVIDE ACCURATE SIZED GROUNDING ELECTRODE |
| | CONDUCTOR. NEC 250.66 |
| | 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. |
| | NEC 110.3, 110.9 |
| | 10. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 11. PROVIDE SPEC SHEET FOR 4000 VA RANGE SPECIFIED IN |
| | LOAD CALCULATIONS. NEC 110.3 |
| | |
| | BE ADVISED THAT THERE SEEMS TO BE A SUBSTANTIAL AMOUNT |
| | OF INFORMATION INCORRECT AND/OR MISSING WITH THIS PLAN. |
| | FUTURE ADDITIONAL COMMENTS ARE POSSIBLE WHEN THE |
| | INFORMATION ABOVE IS SUPPLIED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |