| Plan Review Notes For Permit 17110126 |
| Permit Number |
17110126 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-09-18 13:52:12 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | | EXISTING BUILDING CODES | | | PERMIT #17110126 | | | 9/18/18 | | | | | | 1) THE REVISED PLAN IS STILL INDICATING A 2" CLEARANCE | | | WILL BE PROVIDED AROUND THE AIR HANDLER, HOWEVER 4" IS | | | REQUIRED. | | | | | | 2) THE REQUESTED CORRECTED ENERGY COMPLIANCE FORMS WERE | | | NOT CORRECTED AND RESUBMITTED. | | | | | | 3) THE AC CALCULATIONS ARE BASING DESIGN CONDITIONS ON | | | FT. LAUDERDALE, AND ARE INDICATING TRANE SYSTEMS TO BE | | | INSTALLED, HOWEVER RHEEM SYSTEMS ARE SHOWN ON THE PLAN. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|