| 2018-05-13 10:15:04 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. A0 INDICATES THE BUILDING TYPE AS IIB. PLEASE ADVISE |
| | AS TO HOW ENGINEER HAS MADE THIS DETERMINATION. OUR |
| | RECORDS SHOW TWO RECORDS RESEARCH REQUESTS DONE IN |
| | 2/2017 AND 9/2017, AND THE RECORDS SHOW WOOD FRAME IN |
| | THIS STRUCTURE. ALSO, THE ROOF PERMIT 98090008 HAS A |
| | SPECIFICATION FOR A NAILABLE DECK. |
| | |
| | THE PREVIOUS REVIEWER RELIED ON THIS INFORMATION WHEN |
| | DOING THE REVIEW. FOR A COMBUSTIBLE BUILDING, THE FLAME |
| | SPREAD FOR THE FLOORING UNDERLAYMENT HAS A MORE |
| | STRINGENT REQUIREMENT OF 25 AS OPPOSED TO 200 FOR TYPE |
| | I/TYPE II BUILDINGS. |
| | |
| | WITHOUT ACCURATE INFORMATION, AN ACCURATE CHECKLIST |
| | CANNOT BE PROVIDED AT THIS TIME. HAS ENGINEER BEEN TO |
| | THIS JOB? PROVIDE INFORMATION REGARDING WALL |
| | CONTRUCTION, FLOOR CONSTRUCTION, ROOF CONSTRUCTION. |
| | |
| | 2. FLOORING PROPOSED IS NOT CLEAR. PLEASE ADVISE. A |
| | FLOORING UNDERLAYMENT CANNOT BE REVIEWED UNTIL THE |
| | FLOOR CONSTRUCTION AND FLOORING PROPOSED IS DETERMINED. |
| | |
| | PLEASE NOTE THAT VERY FEW PRODUCTS HAVE THE THREE TESTS |
| | REQUIRED. |
| | |
| | TEST REPORTS ARE REQUIRED - MANUFACTURER SPEC SHEETS |
| | ARE NOT ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC |
| | SHEETS/BROCHURES AND TEST REPORTS FOR SOME |
| | MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER |
| | SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC B 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | EXCEPTION IN FBC B 603.1 IS FOR BUILDING TYPE I & II. |
| | IF THE BUILDING IS III, IV, V, PER FBC B 720.2 FLAME |
| | SPREAD LESS THAN 25 IS REQUIRED. |
| | |
| | |
| | |