| 2018-02-22 17:01:59 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, |
| | EXISTING BUILDING CODES |
| | PERMIT #17110126 |
| | 2/22/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ENERGY COMPLIANCE FORMS AND AND AC CALCULATIONS HAVE |
| | BEEN SUBMIITED FOR FOUR OF THE TWENTY APARTMENTS. THE |
| | UNITS ARE IDENTIFIED AS MODELS 1 & 2 LOW AND HIGH |
| | FLOOR, HOWEVER THE REPORT IS NOT INDICATING THAT THESE |
| | ARE "WORST CASE" CALCULATIONS, THEREFORE CALCULATIONS |
| | SHALL BE SUBMITTED FOR ALL OF THE APARTMENTS. IF THE |
| | CALCULATIONS ARE TO BE PERFORMED AS "WORST CASE" THEN |
| | THE |
| | |
| | REPORTS MUST BE LABELED AS SUCH, AND ALSO DEMONSTRATE |
| | THAT THE MODELS MEET THE PERFORMANCE REQUIREMENTS IN |
| | EACH OF THE FOUR CARDINAL (NORTH, SOUTH, EAST, AND |
| | WEST) ORIENTATIONS- SEE SECTION R405.4.2 FBC-14 ENERGY |
| | CONSERVATION. PLEASE NOTE THE APARTMENT MODEL |
| | IDENTIFICATIONS ( #1 & 2) IN THE CALCS DO NOT MATCH THE |
| | (TYPE A & B) IDENTIFICATIONS ON THE PLANS. |
| | |
| | 2) 2ND REQUEST FOR MINIMUM VENTILATION FOR EACH |
| | APARTMENT USING EITHER MECHANICAL OR NATURAL MEANS- |
| | SECTION 401.2. THE RESUBMITTED PLAN INDICATES NATURAL |
| | FOR APARTMENT TYPE B BUT DOES NOT SHOW THE UNIT |
| | COMPLIES WITH 402.2- MINIMUM OPERABLE AREA TO THE |
| | OUTDOORS SHALL BE 4% OF THE FLOOR AREA. CONCERNING TYPE |
| | A THERE IS NO VENTILATION INDICATED OR CALCULATIONS |
| | PROVIDED. |
| | |
| | 3) INDICATE THE DIEMNSIONS OF THE RETURN GRILL IN THE |
| | KITCHEN/LIVING ROOM OF THE TYPE B MODEL. |
| | |
| | 4) PROVIDE A COMPLETE AC EQUIPMENT SCHEDULE ON THE PLAN |
| | FOR THE MODEL A SYSTEM- COOLING AND HEATING CAPACITY, |
| | SUPPLY CFMS, AND EFFICIENCY RATING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |