| 2017-11-22 13:00:33 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. UNDER THE SCOPE OF WORK IT LIST REPLACE A TANK WATER |
| | HEATER SHT. A-2 SHOWS A TANK WATER HEATER IN THE A UNIT |
| | AND A TANKLESS IN THE B UNITS PLEASE CLARIFY WHICH TYPE |
| | OF WATER HEATERS ARE BEING USED HOW MANY ARE BEING |
| | CHANGED AND IN WHICH APARTMENTS. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 2. PROVIDE EXISTING GAS PIPING DIAGRAM SHOWING TYPE OF |
| | PIPE, SIZE, BTU LOAD, PRESSURE AND APPROXIMATE LENGTH |
| | OF PIPING. PER FBC FG 402.4.1, 402.4.2. AND WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 3. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND |
| | INSTALLATION GUIDES FOR THE WATER HEATERS. PER FBC FG |
| | 402.2 AND WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. WILL THE EXISTING VENTING BE USED IF SO IT SHALL BE |
| | INSPECTED PLEASE PLEASE NOTE ON PLAN STATING THIS. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. WILL THE NEW WATER HEATERS BE EXACT CHANGE OUT FROM |
| | EXISTING PLACE NOTE ON PLAN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 6. A DROPTEST AFFIDAVIT ON THE COMPLETE GAS SYSTEM WILL |
| | BE REQUIRED AT FINAL INSPECTION PLEASE PLACE NOTE ON |
| | PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |