| 2017-11-14 12:31:16 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | 561-805-6667 [email protected] |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| | RESIDENTIAL CODE 2015 5TH EDITION |
| | |
| | 1. PROVIDE TWO COPIES OF THE SOUND PROOFING |
| | SPECIFICATIONS FOR THE SECOND FLOOR APARTMENTS. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2. PERMIT VALUE TOO LOW. ADJUST PERMIT VALUE. FBC 109.3 |
| | BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE |
| | BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 3. SINCE THE VALUE OF THE PROJECT WILL BE ABOVE $25,000 |
| | A DESIGN PROFESSIONAL IS REQUIRED. |
| | DESIGN PROFESSIONAL ? REQUIRED |
| | PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS |
| | DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN MUST BE |
| | PREPARED BY A LICENSED PROFESSIONAL PURSUANT TO FS 481. |
| | SEE BELOW: |
| | |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A |
| | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY |
| | CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA |
| | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES& |
| | 61G1 FLORIDA ADMINISTRATIVE CODE. |
| | |
| | WHERE SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL |
| | IS AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION |
| | DOCUMENTS TO BE PREPARED BY A REGISTERED DESIGN |
| | PROFESSIONAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN REQUIRED BY THE BUILDING OFFICIAL, AND |
| | MAY REQUIRE ONLY ONE SET OF SUBMITTALS. |
| | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, |
| | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE |
| | 61G15-23.001. |
| | DESIGN PROFESSIONAL ? EXCEPTIONS |
| | |
| | FS 481.229 -EXCEPTIONS; EXEMPTIONS FROM LICENSURE. |
| | |
| | (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN |
| | ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS |
| | FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR |
| | ALTERATION OF: |
| | |
| | (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY |
| | FARMER, REGARDLESS OF THE COST OF THE BUILDING; |
| | |
| | (B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING, |
| | TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY |
| | ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST; |
| | OR |
| | |
| | (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN |
| | $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING |
| | INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF |
| | A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR |
| | SCHOOL PROJECTS PURSUANT TO S. 1013.45. |
| | |
| | 4. NOTE SHOWN ON A-3 OTHER AREAS AFFECTED BY THE |
| | ALTERATION. PROVIDE ADDITIONAL INFORMATION. |
| | WILL FRAMING, DRYWALL OR INSULATION BE PART OF THIS |
| | PROJECT? IF SO SHOW ON PLANS THE LOCATION AND EXTENT OF |
| | THIS WORK. SHOW THE EXTERIOR WORK THAT WILL BE |
| | COMPLETED. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |
| | |