| Date |
Text |
| 2018-05-12 05:25:23 | 1) THERE ARE TWO SETS OF PLANS THAT ARE MISSING THE |
| | "CVR" SHEET AND ALSO THE ELECTRICAL PLANS. SUBMIT TWO |
| | COMPLETE SETS OF PLANS FOR REVIEW. WPB AMEND TO FBC |
| | SEC. 107.1. |
| | 2) ONE SET OF PLANS CONTAINS MEP SHEETS THAT ARE NOT |
| | SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. COMPLY |
| | WITH FL. ADMIN. CODE RULE 61G15-23.001. |
| | 3) SHT. A1.0 - DETAIL #3 - ENLARGED PLAN - THE |
| | ELEVATION ARROWS LISTING THE ELEVATION DETAIL DO NOT |
| | CORRELATE WITH THE ELEVATIONS ON THE PLANS AND ALSO |
| | REFER TO SHT. A4 WHICH THERE IS NO SUCH SHEET. REVISE. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SHT. A1.0 - THE OUTLET OF THE TOILET PAPER DISPENSER |
| | IN THE HANDICAPPED TOILET ROOMS SHALL BE LOCATED A |
| | MINIMUM OF 15 INCHES AND A MAXIMUM OF 48 INCHES ABOVE |
| | THE FINISH FLOOR. 2017 FBC-ACCESS. SEC.604.7. SHOW THIS |
| | ON SHT. A1.0. |
| | 5) SHOW THE REQUIRED TURNING SPACE IN RESTROOM #105 IN |
| | ACCORDANCE WITH THE 2017 FBC-ACCESS. SEC.304.1, |
| | 304.3.1, 304.3.2. |
| | 6) SHT. A1.0 - RESTROOM #105 - SHOW THE WIDTH DIMENSION |
| | BETWEEN THE CORNER EDGE OF THE LAVATORY AND THE END OF |
| | THE URINAL PARTITION.COMPLY WITH 2017 FBC-ACCESS. |
| | SEC.305.3. |
| | 7) SUBMIT 2 COMPLETE COPIES OF THE MANUFACTURER'S |
| | INSTALLATION MANUAL FOR THE DISHWASHER. WPB AMEND. TO |
| | FBC SEC. 107.2.1. 2ND REQUEST. |
| | 8) SHT. P-2 - INDICATE ON THE EXPANSION TANK SIZING |
| | CHART ON SHT. P-2 THE SIZE OF THE EXPANSION TANK TO BE |
| | INSTALLED ON THE WATER SUPPLY SYSTEM. |
| | 9) SUBMIT TWO COPIES OF THE INSTALLATION MANUAL FOR THE |
| | WATER FILTRATION SYSTEM. WPB AMEND. TO FBC SEC. |
| | 107.2.1. 2ND REQUEST. |
| | 10) SHT. A1.0 - DETAIL #4 - THE LOCATION OF THE SIDE |
| | GRAB BAR SHALL COMPLY WITH 2017 FBC-ACCESS. |
| | SEC.604.5.1. THE GRAB BAR SHALL EXTEND A MINIMUM OF 54 |
| | INCHES FROM THE REAR WALL. REFER TO 2017 FBC-ACCESS. |
| | FIGURE 604.5.1.3RD REQUEST. |
| | 11) SHT. P-2 - THE DISCHARGE LIINE FROM THE WORK TABLE |
| | IN BOH #103 SHALL BE INDIRECTLY WASTED TO THE GREASY |
| | WASTE SYSTEM PER THE 2017 FBC-PLUMBING SEC.802.2. |
| | 12) SUBMIT AN EXPANDED PIPNG DETAIL / DIAGRAM FOR THE |
| | HOT WATER RECIRCULATION SYSTEM. THE HOT WATER OR |
| | TEMPERED WATER RETURN LINE SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC.607.2.2. A |
| | NOTE HAS BEEN PLACED ON THE PLAN TO THIS EFFECT BUT IS |
| | INADEQUATE. I HAVE INCLUDED A DIAGRAM AND TEXT FROM THE |
| | PLUMBING CODE COMMENTARY IN THE PLAN REVIEW FOLDER FOR |
| | A REFERENCE.2ND REQUEST. |
| | 13) NOTE: ALL PLUMBING PIPES SHALL BE EXPOSED AND |
| | TESTED FOR INSPECTION OR A VIDEO OF SANITARY PIPING |
| | SHALL BE APPROVED BY TIM LARGE FOR THE ROUGH |
| | INSPECTIONS PER FBC PL 312. ROUGH INSPECTION WILL NOT |
| | PASS IF THE VIDEO SSHOWS ANY PORTION OF THE UNDERGROUND |
| | PIPING EXHIBITING NON-COMPLIANCE WITH THE PLUMBING CODE |
| | AND IN THAT INSTANCE THE UNDERSLAB PIPING SHALL BE |
| | EXPOSED FOR AND CORRECTED AND INSPECTED FOR COMPLIANCE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |