| 2018-05-22 13:47:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED |
| | 7. CORRECTED |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. CORRECTED |
| | |
| | NEW COMMENT: |
| | |
| | 13. IT APPEARS THAT THERE IS A TABLE IN FRONT OF |
| | ELECTRICAL PANELS. CLEARANCE IN FRONT OF PANELS IS |
| | REQUIRED PER NEC, PROVIDE CORRECTION. NEC 110.26 |
| | 14. CORRECTED |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR |
| | 561-805-6742 |
| | [email protected] |
| | |
| | |
| 2018-05-15 09:27:24 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| | AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2 |
| | (NOT PROVIDED. A GENERAL NOTE IS NOT ACCEPTABLE, |
| | PROVIDE DETAILS OF LIGHTING CONTROL ON PLAN.) |
| | 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 (NOT |
| | PROVIDED.) |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW |
| | LIGHTING. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN |
| | OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION |
| | OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL |
| | TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN |
| | OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME |
| | SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE |
| | CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING |
| | DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. |
| | FBC CE 405.2.4 (NOT PROVIDED. A GENERAL NOTE IS NOT |
| | ACCEPTABLE, PROVIDE DETAILS OF LIGHTING CONTROL ON |
| | PLAN.) |
| | |
| | NEW COMMENT: |
| | |
| | 13. IT APPEARS THAT THERE IS A TABLE IN FRONT OF |
| | ELECTRICAL PANELS. CLEARANCE IN FRONT OF PANELS IS |
| | REQUIRED PER NEC, PROVIDE CORRECTION. NEC 110.26 |
| | 14. ONLY ONE SET OF PLANS WAS PROVIDED FOR REVIEW, AND |
| | THE PLAN IS NOT SIGNED AND SEALED BY THE DESIGN |
| | PROFESSIONAL. PROVIDE CORRECTION. WPB FBC 107.1, 107.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |