| 2017-11-22 16:58:56 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE PREVIOUS OCCUPANCY OF THIS TENANT SPACE WAS |
| | MERCANTILE WHICH MAKES THIS A CHANGE OF OCCUPANCY |
| | PLEASE REVISE CLASSIFICATION OF WORK AND ALL WORK SHALL |
| | COMPLY WITH FBC EXISTING BUILDING CH 10 |
| | |
| | 2. THE PLAN SHOWS AN EXISTING KITCHEN UPON REVIEW OF |
| | PERMIT RECORDS THERE IS NO PERMITS FOR A KITCHEN AND |
| | TIM LARGE INFORMED ME THAT THEIR IS A CODE VIOLATION |
| | WRITTEN UP FOR WORK WITHOUT PERMITS FOR THE KITCHEN, |
| | BAR AREA, PIZZA OVEN AND BATHROOMS ALL PLUMBING WORK |
| | WILL BE CONSIDERED AS NEW WORK AND SHALL COMPLY WITH |
| | FBC PL, ACC 2014 5TH EDITION |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE |
| | WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| | LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND |
| | EXTENDING 54 INCHES |
| | MINIMUM FROM THE REAR WALL. |
| | |
| | 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR |
| | WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM |
| | AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| | INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| | OTHER SIDE. |
| | |
| | 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS. |
| | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM |
| | MEASURED TO THE TOP OF THE SEAT. |
| | |
| | 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| | DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| | |
| | 7. AT LEAST ONE OF THE URINALS SHALL COMPLY WITH FBC |
| | ACC 605.2 HEIGHT AND DEPTH. |
| | URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE |
| | WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| | OR GROUND. URINALS SHALL BE 131/2 INCHES DEEP MINIMUM |
| | MEASURED FROM THE OUTER FACE OF THE URINAL RIM TO THE |
| | BACK OF THE FIXTURE. |
| | 605.3 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 |
| | POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED. |
| | AND FBC PL 405.3.1 |
| | |
| | 8. PLEASE SHOW COMPLIANCE WITH FBC PL 405.3.5 URINAL |
| | PARTITIONS. |
| | EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL |
| | OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS TO |
| | PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN AT |
| | A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND NOT |
| | LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE. |
| | THE WALLS OR PARTITIONS SHALL EXTEND FROM THE WALL |
| | SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN 18 |
| | INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND THE |
| | OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE |
| | FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. |
| | |
| | 9. A GREASE INTERCEPTOR IS REQUIRED FOR ALL KITCHEN |
| | FIXTURES MINUS ICE MACHINES. PER FBC PL 1003.3.1 |
| | |
| | 10. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR HOT AND |
| | COLD WATER, SANITARY AND GREASY WASTE. PER WPB AMEND TO |
| | FBC 107.3.5.1.3(13) |
| | |
| | 11. PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 12. ALL PLUMBING PIPES SHALL BE EXPOSED AND TESTED FOR |
| | INSPECTION OR A VIDEO OF SANITARY PIPING SHALL BE |
| | APPROVED BY TIM LARGE AND MYSELF FOR THE ROUGH |
| | INSPECTIONS. PER FBC PL 312 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |