| 2017-12-07 15:34:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. | | | THIS MUST BE A DIGITAL SIGNATURE FOR DIGITAL PLANS. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 | | | 2. PROVIDE DETAILS OF WIRING USED FOR SYSTEM, INDICATE | | | IF CABLING IS PLENUM RATED OR NOT. FBC 107.2.1; NEC | | | 800.113 | | | 3. PROVIDE LEGEND FOR DEVICES ON PLAN. FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|