| 2018-05-13 13:05:41 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | ARCHITECT - KEITH SPINA, GLIDDEN SPINA |
| | STRUCTURAL - ANDREW P. SULLIVAN, PE, MCNAMARA-SALVIA |
| | MEP - STEPHEN FELLERS, PE |
| | |
| | FS471, FS481 REQUIRE THAT DOCUMENTS PREPARED BY AN |
| | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED, SEALED, DATED ORIGINALS. |
| | |
| | 1. ARCH, CIVIL OK |
| | |
| | 2. THE NEW PLUMBING PAGES HAVE AN ERROR THAT THE |
| | SIGNATURE IS OK, BUT THERE ARE UNSIGNED CHANGES MADE |
| | AFTER SIGNING. I'VE SEEN THIS ERROR ASSOCIATED WITH |
| | UTILIZING A DIFFERENT SOFTWARE (BLUEBEAM?). |
| | |
| | PLUMBING HAS PASSED REVIEW. PLEASE CONTACT ME VIA EMAIL |
| | TO DISCUSS HOW THIS WILL BE RESOLVED. THIS WILL BE A |
| | PROVISO ITEM. |
| | |
| | 3. THE NEW MECHANICAL PAGES HAVE AN ERROR THAT THE |
| | SIGNATURE IS OK, BUT THERE ARE UNSIGNED CHANGES MADE |
| | AFTER SIGNING. I'VE SEEN THIS ERROR ASSOCIATED WITH |
| | UTILIZING A DIFFERENT SOFTWARE (BLUEBEAM?). |
| | |
| | MECHANICAL HAS FAILED REVIEW. PLEASE CONTACT ME VIA |
| | EMAIL REGARDING HOW THIS WILL BE ADDRESSED. NEW SHEETS |
| | SHOULD HAVE THE SIGNATURE ISSUE CORRECTED, BUT SHEETS |
| | WHICH DO NOT CHANGE SHOULD NOT BE CORRECTED AND |
| | UPLOADED. THE SIGNATURE ERROR ISSUE WILL BE A PROVISO |
| | ITEM. |
| | |
| | AC CALCS PREPARED BY STEPHEN FELLER, PE ARE NOT |
| | DIGITALLY SIGNED AND SEALED. A DIGITALLY SIGNED AND |
| | SEALED DOCUMENT WILL BE REQUIRED AT THE SAME TIME THAT |
| | PLAN PAGES ARE ADDRESSED (PROVISO ITEM). |
| | |
| | SHEETS M5.0.0 (TWO DIFFERENT PAGES WITH SAME NUMBER, |
| | DIFFERENT RISER INFORMATION), M5.0.1, M5.0.2 (TWO |
| | DIFFERENT PAGES WITH SAME NUMBER, DIFFERENT |
| | INFORMATION) |
| | |
| | ENERGY CALCS - OK |
| | FIRE STANDPIPE CALCS - OK |
| | |
| | 4. ELECTRICAL SHEETS OK |
| | |
| | 5. SLS CONSULTING, INC. FIRE PROTECTION ENGINEERS - |
| | SMOKE CONTROL RATIONAL ANALYSIS - OK (4/13/18 VERSION) |
| | |
| | 6. THE COVER SHEET AND INDEX PAGES ARE NUMBERED 570, |
| | 571 AND 572, WHICH WILL MAKE THEM PRINT IN THE MIDDLE |
| | OF THE PLAN SET. ARE THESE DUPLICATES OF THE COVER |
| | SHEET AND INDEX PAGES AT THE BEGINNING OF THE DOCUMENT? |
| | CAN THEY BE VOIDED OR DELETED? |
| | |
| | |
| | |
| | |
| | |
| | |
| | |