| Date |
Text |
| 2018-05-16 16:46:33 | MECHANICAL PLANS APPROVED WITH EXECEPTION AND PROVISOS. |
| | 6/4/18 |
| | |
| | AS OF 6/4/18 THE FOLLOWING LIST OF COMMENTS FROM THE |
| | 3RD REVIEW WERE NOT ADDRESSED, HOWEVER DUE TO THE |
| | URGENT NEED TO HAVE THE PERMIT ISSUED, THE CURRENT |
| | MECHANICAL PLANS AND DOCUMENTS ARE APPROVED WITH |
| | EXCEPTION, AND THE REMAINING COMMENTS LISTED BELOW ARE |
| | DEEMED TO BE PROVISOS TO BE ADDRESSED BY THE DESIGN |
| | PROFESSIONAL AS SOON AS POSSIBLE. |
| | |
| | |
| | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17110075 |
| | 5/16/2018 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE THIRD REVIEW OF THE PLANS IS BASED ON THE |
| | RESUBMITTED PLANS AND DOCUMENTS, AND THE RESPONSES BY |
| | THE ARCHITECT OF RECORD. COMMENTS FROM THE PREVIOUS |
| | REVIEWS THAT HAVE NOT BEEN ADDRESSED, OR PARTIALLY |
| | STILL EXIST WILL BE REITERATED BELOW. |
| | |
| | 1) THE REVISED AC CALCULATIONS ARE NOT ELECTRONICALLY |
| | SIGNED AND SEALED BY THE EOR AS PREVIOUSLY REQUESTED. |
| | |
| | 2) COMMISSIONING OF THE COMMON AREA AC SYSTEMS IS |
| | REQUIRED PER SECTION C.408.2 EXCEPTION #1 FBC-EC. THE |
| | TOTAL BTUH'S OF THE O/A UNIT, THE MINI SPLIT SYSTEMS, |
| | THE COMMON AREA UNITS, THE OLIVE RETAIL SPACE, AND THE |
| | BANYAN RETAIL SPACE= 2,699,303 BTUH WHICH FAR EXCEEDS |
| | THE 480,000 BTUH THRESHOLD FOR COOLING. THE ARCHITECT'S |
| | RESPONSE NARRATIVE INCORRECTLY INDICATES THE |
| | THRESHOLD TO BE AT 400 TONS (4,800,000 BTUH), HOWEVER |
| | PER THE CODE SECTION IT IS 40 TONS (480,000 BTUH). |
| | PLEASE PROVIDE A COMMISSIONING PLAN AS PREVIOUSLY |
| | REQUESTED. |
| | |
| | 8 & 17) THE COMMENT REQUIRING POSITIVE PRESSURIZATION |
| | AND VENTILATION OF THE ELEVATOR LOBBIES IN THE PARKING |
| | GARAGES IS IN DISPUTE BY THE DESIGN PROFESSIONAL OF |
| | RECORD. THIS MATTER WILL BE REFERRED TO THE BUILDING |
| | OFFICIAL FOR REVIEW. |
| | |
| | 9) DUE TO THE FACT THAT THERE ARE DOOR OPENINGS INTO |
| | THE EXIT PASSAGEWAYS USED TO EXTEND STAIRS #1, 2, & 3 |
| | TO THE EXIT DISCHARGE OR PUBLIC WAY, SECTION 1022.10.1 |
| | EXCEPTION 1 REQUIRES THE EXIT PASSAGEWAY TO BE |
| | PRESSURIZED IN THE SAME MANNER AS THE PRESSURIZED |
| | STAIRWAY. THE ADDITIONAL NOTE ON SHEET M5.03 ABOUT THE |
| | EXIT PASSAGEWAY PRESSURIZATION MUST BE MODIFIED TO |
| | PROVIDE THE REQUIRED PRESSURIZATION PARAMETERS OF 0.10 |
| | IN. WG TO MAXIMUM 0.35 IN. WG. THIS MODIFICATION ALSO |
| | APPLIES TO THE NEW NOTE ON PAGE 7 OF THE SLS SMOKE |
| | CONTROL RATIONAL ANALYSIS REPORT. THE TERM "EXIT |
| | CORRIDOR" USED IN THE ANALYSIS IS INCORRECT, AND SHOULD |
| | BE REVISED TO READ "EXIT PASSAGEWAY". PLEASE NOTE THAT |
| | FIELD TESTING MUST VERIFY THAT THE PRESSURIZATIONS IN |
| | THE PASSAGEWAYS ARE EQUIVALENT TO THE STAIRWAYS. |
| | |
| | 14) SHEET M1.2.1A: PLEASE MODIFY THE GENERATOR EXHAUST |
| | DISCHARGE NOTE TO INCLUDE THE REQUIRED 10' CLEARANCE TO |
| | PROPERTY LINES, OPERABLE OPENINGS, AND TO GRADE. |
| | |
| | 15) M4.01, M4.02: STRUCTURAL ENGINEERING REQUIRED FOR |
| | ATTACHING THE AC AND INLINE FAN SUPPORTS TO THE SLAB |
| | WILL BE A DEFERRED SUBMITTAL. THE ENGINEERING SHALL BE |
| | PROVIDED PRIOR TO INSPECTION, AND BE ONSITE AT TIME OF |
| | INSPECTION. |
| | |
| | 22) COMMENT #44 STILL EXISTS. WIND LOAD ENGINEERING FOR |
| | INSTALLATION OF THE EXTERIOR BARBECUE NOT PROVIDED BUT |
| | MAY BE A DEFERRED SUBMITTAL. THE SUBMITTED CUT SHEET |
| | FOR THE BARBECUE DOES NOT INDICATE THE APPLIANCE HAS |
| | BEEN TESTED IN ACCORDANCE WITH THE ANSI STANDARDS |
| | LISTED UNDER SECTION 623.1 FBC-14 FUEL GAS. |
| | |
| | 24) COMMENT STILL EXISTS. THE NARRATIVE INDICATES THE |
| | FIRESTOPPING DETAIL FOR THE REFRIGERANT PIPING TO BE ON |
| | M.5.0.2, HOWEVER M5.02 IS A CONTROL PAGE AND THE DETAIL |
| | IS NOT SHOWN THERE. |
| | |
| | 28) SHEET M2.9.1 NOT ELECTRONICALLY SIGNED AND SEALED. |
| | |
| | 29) THE ENLARGED 16"X6" TRANSFER DUCT IS UNDERSIZED- |
| | MINIMUM 108 SQ. INCHES REQUIRED. SHEET M2.10.1 NOT |
| | ELECTRONICALLY SIGNED AND SEALED. |
| | |
| | 30) SHEET M2.15.1 NOT ELECTRONICALLY SIGNED AND SEALED. |
| | |
| | 31) SHEET M2.21.1 NOT ELECTRONICALLY SIGNED AND SEALED. |
| | 32) SHEET M2.27.1 NOT ELECTRONICALLY SIGNED AND SEALED. |
| | |
| | 33) SHEET M2.28.1 NOT ELECTRONICALLY SIGNED AND SEALED. |
| | |
| | 34) SHEET M2.30.1, UNIT 1039:- CANNOT VERIFY CORRECT |
| | SIZING OF THE RETURN TRANSFER DUCT BECAUSE THE SIZE OF |
| | THE SUPPLY DUCT INTO THE MASTER SUITE IS NOT INDICATED. |
| | |
| | 34) SHEET M2.30.1, UNIT 1008: THE 16"X6" RETURN |
| | TRANSFER DUCT FROM THE MASTER SUITE IS UNDERSIZED- 120 |
| | SQ. INCHES REQUIRED. |
| | NEW COMMENTS. |
| | |
| | 1) ADVISORY: TO AVOID A CONFLICT IN THE FIELD, PLEASE |
| | REVIEW PLANS AND PROVIDE DUCT SMOKE DETECTORS IN THE |
| | RETURN SYSTEMS OF ANY AC SYSTEMS IN THE APARTMENTS OR |
| | IN THE COMMON AREAS WITH MINIMUM 5-TON CAPACITIES. |
| | |
| | 2) SHEET M.401: PROVIDE A NOTE IN THE SCHEDULE TO |
| | INDICATE THAT ANY SMOKE CONTROL FANS THAT ARE |
| | BELT-DRIVEN SHALL BE EQUIPPED WITH A MINIMUM OF TWO |
| | BELTS- SECTION 513.10.5. THIS WOULD INCLUDE BOTH |
| | PRESSURIZATION AND EXHAUST FANS. |
| | |
| | 3) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR |
| | THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING |
| | APPROVAL BY THE ENGINEER OF RECORD: |
| | |
| | A) SMOKE CONTROL FANS. |
| | B) FIRE AND FIRE/SMOKE DAMPERS. |
| | C) BAROMETRIC DAMPERS |
| | D) DUCT SMOKE DETECTORS |
| | E) AC ROOF AND DUCT STANDS, WALL BRACKETS |
| | F) EXHAUST AND OUTSIDE AIR LOUVERS |
| | G) C02 AND N02 SENSORS |
| | H) PIPING INSULATIONS |
| | I) ACCESS PANELS |
| | J) GENERATOR |
| | K) COMMERCIAL CLOTHES DRYERS |
| | L) COOKING APPLIANCES |
| | M) DUCT FIRE WRAPPING |
| | N) FIRESTOPPING AND FIRE CAULKING |
| | O) MANUFACTURER'S SPECIFICATIONS AND WIND LOAD |
| | ENGINEERING FOR THE EXTERIOR BARBECUE. |
| | P) STRUCTURAL DETAILS FOR ATTACHING THE AC UNITS AND |
| | INLINE FAN SUPPORTS TO THE SLAB. |
| | Q) WIND LOAD ENGINEERING FOR ALL ROOF TOP MOUNTED |
| | MECHANICAL EQUIPMENT- OAU'S, FANS AND FAN CURBS, AC |
| | STANDS, SUPPORTS ETC. |
| | R) MANUFACTURER'S CERTIFICATION AND INSTALLATION |
| | INSTRUCTIONS FOR THE OUTDOOR CONDENSERS TO BE INSTALLED |
| | IN THE ENCLOSED PARKING GARAGE |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |