| 2018-02-20 08:18:47 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P1.1.1A, B, C, D THE SANITARY STACKS ARE |
| | LABELED ALL THE SAME MATCHING THE NOTES PLEASE LABEL TO |
| | MATCH THE ISOMETRIC DRAWINGS. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | 2. IF YOU ARE CAPPING THE GREASE WASTE UNDER THE SLAB |
| | PLEASE INDICATE ON THE PLAN HOW IT WILL BE LOCATED IN |
| | THE FUTURE. PER WPB AMEND TO FBC 107.2.1 |
| | 3. SHT. P3.1.1 IT APPEARS THAT SANITARY STACK #17 IS |
| | LABELED AS #19 PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 4. SHT. P3.1.1 THE 4? BUILDING DRAIN BETWEEN STACK #26 |
| | AND #27 IS UNDER SIZED. PER FBC PL TABLE 710.1(1) |
| | 5. SHT. P1.1.1A, B, C, D, PLEASE LABEL THE STORM RISERS |
| | TO MATCH THE ISOMETRIC DRAWINGS ON P3.11.1 PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 6. SHT. P1.1.1D NOTE #3 LIST A 15? STORM DRAIN THE |
| | ISOMETRIC ON P3.11.1 SHOWS A 16? THE 15? IS UNDER |
| | SIZED. PER FBC PL TABLE 1106.3 |
| | 7. SHT. P1.1.1D NOTE #7 LIST 12? STORM THE ISO SHOWS |
| | 16? PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | 8. IN PREVIOUS COMMENT #30 IS WAS ASKING FOR THE SPECS |
| | FOR THE PUMPS YOUR RESPONSE WAS FOR THE GREASE |
| | INTERCEPTOR I STILL NEED THOSE SPECS FOR THE BOOSTER |
| | PUMPS THE CAN BE SUBMITTALS IF YOU REQUESTED. PER WPB |
| | AMEND TO FBC 107.3.4.2 |
| | 9. SHT. P3.13.1 THE 8? HORIZONTAL STORM DRAIN BETWEEN |
| | RISER E AND F IS UNDER SIZED THE MAX SQFT FOR 8? @ |
| | 1/8FT IS 9200SQFT. PER FBC PL TABLE 1106.2 |
| | 10. PER FBC PL SIZING TABLE 1106.2 IT ONLY GOES UP TO |
| | 15? PLEASE PROVIDE THE CALCULATION TO SIZE THE 16? |
| | STORM. PER WPB AMEND TO FBC 107.2.1 |
| | 11. IN THE SPEC B BATHROOMS SUCH AS THE MASTER IN UNIT |
| | 01 D1-1 WHERE THE TOILET IS ADJACENT TO A SHOWER |
| | BACKING OR REINFORCEMENT WILL BE REQUIRED FOR A FOLD UP |
| | GRAB BAR PLEASE PROVIDE A DETAIL SHOWING THE DIMENSIONS |
| | AND HOW THIS WILL BE DONE. PER FHA DESIGN MANUAL |
| | REQUIREMENT #6 PG 6.6+6.7 |
| | 12. IT APPEARS THAT YOU ARE USING MULTIPLE SAFE HARBOR |
| | DESIGN DOCUMENTS IT IS MY UNDERSTANDING THAT A PROJECT |
| | SHOULD BE DESIGNED USING ONLY 1 SPECIFIC DESIGN |
| | DOCUMENT PLEASE CLARIFY . |
| | 13. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACE |
| | AT THE FIXTURES. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |