| Plan Review Notes For Permit 17110075 |
| Permit Number |
17110075 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-20 08:33:44 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | | | | | | | GAS COMMENTS: | | | PREVIOUS COMMENT 2ND REQUEST 1. KEY NOTE LIST THE | | | RETAIL METER AS #14 THE PLAN SHOWS IT AS #16 PLEASE | | | CLARIFY. AMEND TO FBC 107.2.1 METERS STILL LABELED THE | | | SAME. | | | | | | NEW COMMENTS: | | | | | | 1. PROVIDE INSTALLATION GUIDE FOR POOL HEATER VENTING | | | AND MANUFACTURE SPECIFICATIONS FOR REGULATORS. THESE | | | CAN BE DIFFERED SUBMITTALS IF REQUESTED. | | | | | | 2. THE LONGEST RUN AFTER THE REGULATOR ON THE POOL | | | HEATER IS LISTED AT 25' PER FBC FG TABLE 402.5(2) THE | | | MAX FOR THAT RUN AT 1" WOULD BE 374,000 BTU IT SHALL BE | | | 11/4 AT 25' FOR A LOAD OF 400,000 BTU | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|