| 2018-02-06 14:30:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | THE COMMENTS POSTED BY WESLEY JOLIN HAVE BEED ADDRESSED |
| | EXCEPT FOR THOSE REGARDING THE EXTERIOR BBQ GRILLS. |
| | |
| | THE USE OF BBQ GRILLS ON THE DECK OF A HIGH RISE |
| | BUILDING IS NOT TAKEN LIGHTLY BY THIS OFFICE. THERE ARE |
| | VARIOUS CONCERNS RELATING TO THE SAFE USE OF NG, LEAK |
| | DETECTION/VENTILATION, EMERGENCY SHUTOFF, SMOKE |
| | GENERATION OF EXCESSIVE FATTY PRODUCTS, MISUSE, |
| | LOCATION OF NEARBY COMBUSTIBLES (INCLUDING LANDSCAPE), |
| | POSTING OF USE, SHUTOFF, AND LIGHTING |
| | INSTRUCTIONS,ETC,. |
| | |
| | THIS OFFICE IS NOT AGAINST THE RECREATIONAL USE OF |
| | GRILLS IN THESE AREAS; HOWEVER, IT MUST BE DONE WITH |
| | EXTENSIVE PLANNING AND CONTROL TO ELIMINATE OR REDUCE |
| | AS MANY PREVENTABLE FACTOR FACTORS AS POSSIBLE. |
| | |
| | IT IS THIS WITH MINDSET THAT THESE COMMENTS ARE POSTED |
| | GOING FORWARD. |
| | |
| | IT IS IMPERATIVE AND OF THE UTMOST PRIORITY THAT THE |
| | SAFETY OF THE TENANTS AND VISITORS AND THE SAFETY OF |
| | THIS BUILDING THAT WE WORK TO FIND THAT SAFEST LOCATION |
| | AND PROCEDURES FOR THE USE OF THESE BBQ GRILLS. |
| | |
| | |
| | 1) COMMENT # 4 - INDICATES THAT A GRILL WAS MOVED TO AN |
| | ALTERANTE POCATION. THIS NEW LOCATION IS ONLY SHOWN ON |
| | SHEET A 9.75.2, ALL OTHER RELATED SHEETS IT REMIANS. |
| | |
| | PLEASE CORRECT ALL SHEETS TO AVOID CONFUSION. |
| | |
| | |
| | |
| | 2) COMMENT # 4 - ONLY INDICATES THE RELOCATION OF |
| | ONE(1) GRILL. TWO(2) OTHER GRILLS REMAIN IN THE SAME |
| | LOCATION THAT APPEAR TO BE WITHIN 10FT OF THE "LINE OF |
| | BALCONY ABOVE". |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET A 9.76.1 - THERE IS AN INDICATION OF "STAND |
| | ALONE GRILL" IN TWO (2) LOCATIONS. PLEASE DEFINE THIS |
| | TERM. |
| | |
| | PLEASE BEAR IN MIND THAT LP TANKS SHALL NOT BE USED IN |
| | OR ON THIS AREA, OR STORED AT ANY LOCATION. |
| | |
| | |
| | |
| | 4) THERE ARE NO CLEAR INDICATIONS THAT I WAS ABLE TO |
| | FIND SHOWING THE INSTALLATION OF PORTABLE FIRE |
| | EXTINGUISHERS AT ANY OF THE LOCATION NOTED ABOVE. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | 5) I AM AVAILBLE TO MEET AND REVIEW ANY PROOSED NEW |
| | LOCATIONS OR DISCUSS ANY CONCERNS. IN AN EFFORT TO SAVE |
| | TIME AND ENERGY, PLEASE ALSO USE MY EMAIL ADDRESS TO |
| | SEND ANY PDF'S OR QUESTIONS. |
| | |
| | |
| | |
| | 6) ADDITIONALLY, IN AN EFFORT TO MOVE THIS PROJECT |
| | ALONG, I AM ALSO OPEN TO PROVISING THESE COMMENTS |
| | SHOULD WE AGREE TO ADDRESS THEM AND THEN REVISING |
| | DOCUMENTS TO REFLECT CHANGES. |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |