| 2017-11-29 09:56:17 | 290 NORTH OLIVE AVENUE - APARTMENTS/PARKING GARAGE |
| | PERMIT #17110075 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | |
| | SHEET A1.11.1.A: SUMBIT PRODUCT AND LISTING DATA FOR |
| | PREFABRICATED FIRE TABLE. NOTE: NO OPEN FLAME WILL BE |
| | PERMITTED BY THIS OFFICE. |
| | |
| | SHEET A1.11.1.A: OUTDOOR GRILLS (X2) - PER NFPA 1 |
| | SECTION 10.11.6.1 NO HIBACHI, GRILL, OR OTHER SIMILAR |
| | DEVICES USED FOR COOKING, HEATING, OR ANY OTHER PURPOSE |
| | SHALL BE USED OR KINDLED ON ANY BALCONY, UNDER ANY |
| | OVERHANGING PORTION, OR WITHIN 10 FEET OF ANY |
| | STRUCTURE. |
| | |
| | SHEET A9.75.2: SUMBIT PRODUCT AND LISTING DATA FOR FIRE |
| | PIT. NOTE: NO OPEN FLAME WILL BE PERMITTED BY THIS |
| | OFFICE. |
| | |
| | SHEET A9.75.3: OUTDOOR GRILLS (X3) - PER NFPA 1 SECTION |
| | 10.11.6.1 NO HIBACHI, GRILL, OR OTHER SIMILAR DEVICES |
| | USED FOR COOKING, HEATING, OR ANY OTHER PURPOSE SHALL |
| | BE USED OR KINDLED ON ANY BALCONY, UNDER ANY |
| | OVERHANGING PORTION, OR WITHIN 10 FEET OF ANY |
| | STRUCTURE. |
| | |
| | SHEET M1.11.1.A: SMOKE EXHAUST FAN #1 DISCHARGE IS |
| | LOCATED WITHIN 6 FEET OF THE FRESH AIR INTAKE LOUVER OF |
| | STAIRWELL PRESSURIZATION FAN #1. TO MY KNOWLEDGE, THE |
| | CODE DOES NOT PROVIDE A REQUIRE A PRESCRIBED SEPARATION |
| | DISTANCE, ONLY THAT THE SEPARATION DISTANCE IS |
| | "ADEQUATE." PLEASE PROVIDE A SUPPORTING ARGUMENT AND |
| | DOCUMENTATION ENSURING 6 FEET OF CLEARANCE IS ADEQUATE |
| | SEPARATION TO AVOID SMOKE BEING TRANSFERRED INTO THE |
| | EXIT STAIRWELL. |
| | |
| | SHEETS M5.0.0, M5.0.1, AND M5.0.2 ARE SUBMITTED TWICE. |
| | |
| | SHEET P1.1.2B AND P1.1.2C: PLUMBING PIPING IS BEING |
| | ROUTED THROUGH THE FIRE RATED STAIR EXIT PASSAGEWAY. |
| | PROVIDE A 2-HOUR CEILING IN THE EXIT PASSAGEWAY OR |
| | REROUTE THE PLUMBING PIPING PER NFPA 101 SECTION |
| | 7.1.3.2. |
| | |
| | SHEET E1.1.1: ELECTRICAL FEEDERS RUN THROUGH STAIRWELL |
| | #2 EXIT PASSAGEWAY. PROVIDE A 2-HOUR CEILING IN THE |
| | EXIT PASSAGEWAY OR REROUTE THE ELECTRICAL FEEDERS PER |
| | NFPA 101 SECTION 7.1.3.2. |
| | |
| | SHEET E1.11.1C AND E1.11.1D: ADDITIONAL ILLUMINATED |
| | EXIT SIGNS ARE NEEDED ALONG THE EXTERIOR ROOF EGRESS |
| | PATH TO DIRECT OCCUPANT IN BOTH DIRECTIONS TO THE |
| | STAIRS AS THIS PATH WILL BE UNFAMILIAR TO MOST |
| | RESIDENTS. |
| | |
| | SHEET E3.0.0: PROVIDE MANUAL START AND TRANSFER |
| | FEATURES IN COMMAND ROOM FOR EMERGENCY GENERATOR PER |
| | NFPA 1 SECTION 11.9.5. |
| | |
| | GENERAL: IN SUPPORT OF THE FIRE DEPARTMENT'S GOAL TO |
| | REDUCE NUISANCE AND FALSE FIRE ALARM CALLS, THIS OFFICE |
| | SUGGESTS THE FIRE ALARM SYSTEM BE PROGRAMMED WITH ALARM |
| | VERFICATION WITH 30-60 SECOND DELAY PER NFPA 72. (A |
| | FEATURE OF AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS |
| | TO REDUCE UNWANTED ALARMS WHEREIN SMOKE DETECTORS |
| | REPORT ALARM CONDITIONS FOR A MINIMUM |
| | PERIOD OF TIME, OR CONFIRM ALARM CONDITIONS WITHIN A |
| | GIVEN TIME PERIOD AFTER BEING RESET, IN ORDER TO BE |
| | ACCEPTED AS A VALID ALARM INITIATION SIGNAL.) |
| | |
| | SHEET FA1.1.1A: NO NOTIFICATION APPLIANCE PROVIDED IN |
| | PBULIC RESTROOM #100J. |
| | |
| | SHEET FA1.1.1B: NO NOTIFICATION APPLIANCES PROVIDED IN |
| | SEVERAL ROOMS SUCH AS TELEPHONE, STORAGE, AND |
| | SWITCHGEAR ROOMS. HOW WILL THIS DESIGN MEET THE |
| | AUDIBILITY REQUIREMENTS OF NFPA 72? |
| | |
| | SHEET FA1.1.1B: SEVERAL ROOM AND PARKING GARAGE VISUAL |
| | NOTICATION APPLIANCES APPEAR TO BE COVERING AREAS |
| | GREATER THAN THE LISTING OF THE APPLIANCE. FOR EXAMPLE, |
| | THE SPEAKER-STROBE APPLIANCE LOCATED ON THE CORRIDOR |
| | WALL OF STAIR #2 EXIT PASSAGEWAY IS COVERING NEARLY 50 |
| | FEET. A 75CD WALL MOUNTED STROBE WOULD COVER |
| | APPROXIMATELY 24 FEET. |
| | |
| | SHEET FA1.1.1C: MANUAL PULL STATIONS ARE LOCATED 6-FEET |
| | FROM THE EXIT DOORS FOR THE TWO DOUBLE EGRESS DOORS IN |
| | OLIVE RETAIL AND BANYAN RETAIL SPACES. PER NFPA 72 |
| | SECTION 17.14.6 MANUAL FIRE ALARM BOXES SHALL BE |
| | LOCATED WITHIN 60-INCHES OF THE EXIT DOORWAY OPENING AT |
| | EACH EXIT ON EACH FLOOR. |
| | |
| | SHEET FA1.1.1D: MANUAL PULL STATIONS ARE LOCATED 6-FEET |
| | FROM THE EXIT DOORS FOR THE TWO DOUBLE EGRESS DOORS |
| | BANYAN RETAIL SPACE. NO NOTIFICATION APPLIANCE PROVIDED |
| | IN EXIT PASSAGEWAY #107. SEVERAL PARKING GARAGE VISUAL |
| | NOTICATION APPLIANCES APPEAR TO BE COVERING AREAS |
| | GREATER THAN THE LISTING OF THE APPLIANCE. **CHECK |
| | COVERAGES THROUGHOUT PARKING GARAGE; ALL LEVELS. |
| | |
| | SHEET FA1.2.1A: NO SMOKE DETECTOR PROVIDED IN LOBBY FOR |
| | PHASE I ELEVATOR RECALL. |
| | |
| | SHEET FA1.5.1D: NO NOTIFICATION APPLIANCES PROVIDED IN |
| | MENS' RESTROOM, WOMENS' RESTROOM OR POOL EQUIPMENT |
| | ROOM. |
| | |
| | SHEET FA1.11.1A: INSUFFICIENT NOTIFICATION APPLIANCES |
| | PROVIDED FOR SOUTHEAST AND SOUTHWEST AREAS OF THE ROOF |
| | ASSEMBLY SPACE. |
| | |
| | SHEET FA1.11.1C: NO NOTIFICATION APPLIANCES PROVIDED |
| | ALONG ROOF EGRESS PATH LEADING TO STAIR #3. |
| | |
| | SHEET FP4.0.1: INDICATE ON THE RISERS UP TO WHAT LEVELS |
| | THE PRESSURE REDUCING TYPE VALVES WILL BE UTILIZED ON |
| | THE SPRINKLER AND STANDPIPE SYSTEMS. |
| | |
| | NOTE: THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION |
| | TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO |
| | "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC |
| | SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION |
| | REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION |
| | TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND |
| | COMPLIANCE WITH THE FOLLOWING: |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| | PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |