| Plan Review Notes For Permit 17110057 |
| Permit Number |
17110057 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-13 17:50:21 | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING (ADDED (8) WINDOW REPLACEMENTS TO | | | SCOPE OF WORK) | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | 1) THE INCREASED VALUE OF $200.00 TO REPLACE (8) | | | NON-IMPACT RATED WINDOWS IS TOO LOW. THE COSTS TO | | | PURCHASE AND INSTALL NON-IMPACT SINGLE HUNG WINDOWS PER | | | MARSHALL & SWIFT IS $1202.00. THIS AMOUNT WILL BE ADDED | | | TO THE TOTAL VALUATION. FBC 109.3 | | | | | | 2) FBC -R310.1 REQUIRES EVERY SLEEPING ROOM TO HAVE AT | | | LEAST ONE OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING. | | | IN ORDER TO VERIFY, PROVIDE A FLOOR PLAN WITH THE ROOM | | | TYPES LABELED AND THE EXISTING WINDOW TYPES. FBC | | | 107.2.1 | | | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR | | | NON-IMPACT RATED WINDOWS. SHOW COMPLIANCE WITH | | | FBC-R301.2.1.2 FOR IMPACT PROTECTION. INDICATE ON THE | | | PLANS IF THERE IS EXISTING STORM PANELS OR PROVIDE | | | CALCULATIONS TO SHOW THAT THE AGGREGATE AREA OF THE | | | GLAZING IN THE REPLACED COMPONENTS DOES NOT EXCEED 25 | | | PERCENT OF THE AGGREGATE AREA OF THE GLAZED OPENINGS IN | | | THE DWELLING OR DWELLING UNIT PER THE EXCEPTION TO FBC | | | EXISTING BUILDING SECTION 706.4. | | | |
|