| Plan Review Notes For Permit 17110040 |
| Permit Number |
17110040 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-12-19 09:24:09 | ****PROVISOS**** | | | SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION MAY | | | BE REQUIRED | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. PROVIDE A DETAIL FOR THE PROPOSED NEW BENCH | | | INCLUDING BACK SUPPORT, FBC A 903. | | | | | | 2ND REVIEW, RESPONSE REFERS TO A 7 A202. THIS IS THE | | | SERVICE COUNTER DETAIL. | | | | | | 2. A202, FBC A 904, PROVIDE A DETAIL FOR THE SERVICE | | | COUNTER. CUSTOMER SIDE NOT TO EXCEED 2'6". | | | | | | 3. PER ARCHITECT, UNIT 109 (SHEET A205) HAS BEEN | | | REVIEWED UNDER A DIFFERENT PERMIT AND WAS SUBMITTED IN | | | ERROR. THIS SHEET HAS BEEN VOIDED. | | | | | | |
|