| Plan Review Notes For Permit 17110040 |
| Permit Number |
17110040 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-15 09:51:57 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHEET E1.2, LIGHT IN STORAGE CLOSET SHOULD BE | | | CONTROLLED AUTOMATICALLY. FBC CE 405.2.2 | | | 2. SHEET E1.6 IS FOR UNIT 110, WHICH IS NOT INCLUDED | | | WITH THIS PERMIT NUMBER. ADDITIONALLY, SHEET ER.1 SHOWS | | | REVISIONS TO UNITS 107 AND 110, WHICH ARE NOT INCLUDED | | | WITH THIS PERMIT NUMBER. REMOVE ALL REVISIONS UNDER | | | SEPARATE PERMITS, WHICH SHOULD BE SUBMITTED SEPARATELY. | | | FBC 107.2.1, 107.4 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|