| Plan Review Notes For Permit 17110040 |
| Permit Number |
17110040 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-27 09:27:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FBC 107, PLEASE RESOLVE ADDRESSING ISSUE. OUR SYSTEM | | | HAS DIFFERENT UNIT NUMBERS THAN ON THE PLAN AND | | | APPLICATION, WHICH ALS APPEAR TO DIFFER FROM PROPERTY | | | APPRAISER. PLEASE CONTACT [email protected] TO RESOLVE. | | | | | | 2. SEE ELECTRICAL COMMENTS; IT APPEARS THAT TWO UNITS | | | ARE BEING REVISED. A SEPARATE PERMIT IS REQUIRED FOR | | | EACH PARCEL ID NUMBER. | | | | | | 3. PROVIDE A DETAIL FOR THE PROPOSED NEW BENCH | | | INCLUDING BACK SUPPORT, FBC A 903. | | | | | | 4. REAR EXIT DOORS, UNITS 106 AND 109, REVISE PLAN TO | | | SHOW 18" MANEUVERING CLEARANCE ON THE PULL SIDE, FBC A | | | FIGURE 404.2.4.1(A). | | | | | | 5. A205, DOOR 109B, REVISE PLAN TO SHOW 18" MANEUVERING | | | CLEARANCE ON THE PULL SIDE, FBC A FIGURE 404.2.4.1(A). | | | | | | 6. A202, FBC A 904, REVISE PLAN TO INCLUDE A DETAIL FOR | | | THE SERVICE COUNTER. | | | | | | |
|