2018-06-11 17:30:563RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17110021
 6/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED ENERGY FORM C402-2014 IS FOR
 ALTERATIONS, RENOVATED BUILDINGS, OR BUILDING SYSTEMS.
 THE PROPOSED PROJECT IS A NEW BUILDING SO THE
 ENERGYGAUGE OR COMCHECK SOFTWARE MUST BE USED TO SHOW
 COMPLIANCE FOR A NEW FINISHED BUILDING- SECTION
 C101.5.1 FBC-14 ENERGY CONSERVATION.
  
 2) SHEET M1: THE O/A SCHEDULE INDICATES MECHANICAL
 VENTILATION FOR THE BUILDING HOWEVER NO OUTDOOR AIR HAS
 BEEN PROVIDED MECHANICALLY. IF THE INTENTION IS TO USE
 NATURAL VENTILATION PLEASE SEE SECTION 402 AND PROVIDE
 A CALCULATION USING THE OPERABLE OPENINGS.
  
 3) ELECTRONIC SIGNATURES ARE NOT ACCEPTABLE FOR USE ON
 HARD COPY PAPER PLANS- SECTION 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE. AS PREVIOUSLY REQUESTED THE
 CONTRACTOR OF RECORD SHALL PROVIDE HIS "SIGNATURE" (NOT
 AN ENGINEER'S SEAL AND SIGNATURE) ON THE PLANS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
  
 RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC-14.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  