| 2018-06-11 17:30:56 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17110021 |
| | 6/11/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED ENERGY FORM C402-2014 IS FOR |
| | ALTERATIONS, RENOVATED BUILDINGS, OR BUILDING SYSTEMS. |
| | THE PROPOSED PROJECT IS A NEW BUILDING SO THE |
| | ENERGYGAUGE OR COMCHECK SOFTWARE MUST BE USED TO SHOW |
| | COMPLIANCE FOR A NEW FINISHED BUILDING- SECTION |
| | C101.5.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | 2) SHEET M1: THE O/A SCHEDULE INDICATES MECHANICAL |
| | VENTILATION FOR THE BUILDING HOWEVER NO OUTDOOR AIR HAS |
| | BEEN PROVIDED MECHANICALLY. IF THE INTENTION IS TO USE |
| | NATURAL VENTILATION PLEASE SEE SECTION 402 AND PROVIDE |
| | A CALCULATION USING THE OPERABLE OPENINGS. |
| | |
| | 3) ELECTRONIC SIGNATURES ARE NOT ACCEPTABLE FOR USE ON |
| | HARD COPY PAPER PLANS- SECTION 61G15-23.005 FLORIDA |
| | ADMINISTRATIVE CODE. AS PREVIOUSLY REQUESTED THE |
| | CONTRACTOR OF RECORD SHALL PROVIDE HIS "SIGNATURE" (NOT |
| | AN ENGINEER'S SEAL AND SIGNATURE) ON THE PLANS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | |
| | RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB |
| | AMENDMENTS TO THE FBC-14. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |