2017-12-05 16:18:272014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110021
 ADD: 3200 N. CONGRESS AVE.
 CONT: SOBEL CO.
 TEL: 954-410-9239
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. DEC. 05/ 2017
 ACTION: DENIED
  
 1) SHEET A-0.0.0.1:
  
 1A) PLEASE NOTE THE CITY CONVERTED FROM NGVD 29 TO NAVD
 88 AND THE NEW FEMA FLOOD MAPS ON OCT. 12/ 2017. IN
 DOING SO ALL ELEVATIONS SHOULD BE GIVEN IN NAVD 88.
 ELEVATIONS ON THIS PLAN ARE IN NAVD. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) SHEET A-0.0.0.1 UNDER THE HEADING BUILDING CODE
 DATA REFERENCES THE 2014 FBC-RESIDENTIAL CODE AND MAKES
 REFERENCE TO THE RESIDENTIAL CODE 28 TIMES. THIS
 STRUCTURE IS NOT A RESIDENTIAL DWELLING AND ALL
 REFERENCES TO THE CODE SHOULD BE TO THE 2014 FBC-B AND
 AN OCCUPANCY TYPE PROVIDED.
 2014 FBC-B SECTION 302.1. STRUCTURES SHALL BE
 CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF
 THE GROUPS LISTED IN THIS SECTION.
  
 1C) UNDER THE APPLICABLE CODES THE REFERENCE IS MADE TO
 THE FBC-RESIDENTIAL CODE, PLEASE CORRECT TO THE 2014
 FBC-B.
  
 1D) THE PLAN DOES NOT PROVIDE WHAT THE MINIMUM TYPE OF
 CONSTRUCTION THIS STRUCTURE WAS DESIGNED TOO, SEE 2014
 FBC-B TABLE 503 & TABLE 601.
  
 2) SHEET A1.3.04 FRONT ENTRY SIGNS, MONUMENT SIGNS ARE
 NOT PART OF THIS PERMIT AND WOULD REQUIRE A SEPARATE
 REVIEW AND ASSOCIATED FEES.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 105.1 REQUIRED. ANY CONTRACTOR, OWNER,
 OR AGENT AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE
 489 WHO INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR,
 MOVE, DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING
 OR STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER,
 REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT RESISTANT
 COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR
 FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD
 RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS
 REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE
 DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING
 OFFICIAL AND OBTAIN THE REQUIRED PERMIT.
  
 3A) SHEET A-2.1.01 IS THE ELEVATIONS OF THE GUARD
 HOUSE. THERE IS A COVER SHEET LISTING THE PRODUCT
 APPROVALS TO BE USE FOR THIS STRUCTURE, I BELIEVE THIS
 IS A GENERIC COVER SHEET FOR THE PRODUCT APPROVALS
 SINCE THERE IS A AMARR GARAGE DOOR (NOA 13-0503.06) AND
 A FIXED WINDOW (NOA 14-0908.18) FIXED WINDOW THAT DO
 NOT APPEAR IN EITHER THE FLOOR PLAN OR ELEVATIONS.
 PLEASE UPDATE TO THE CURRENT COMPONENTS AND CLADDING
 FOR THE STRUCTURE. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED, DISCREPANCY IN THE PROVIDED INFORMATION.
  
 3B) THE ELEVATIONS ON SHEET A-2.1.0.1 SHOW ROOF TILE
 BUT THEY DOES NOT INDICATE IF THE O?HAGINS CLOCKED VENT
 TILE, OFF RIDGE VENT IS TO BE INSTALLED ON THIS
 BUILDING? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4A) DISCREPANCY IN PLANS. SHEET A-2.1.01 AND A-6.1.01
 THE TOP OF THE WINDOW DOES NOT MATCH UP. SHEET A-2.1.01
 SECTION # 2 THE TOP OF THE WINDOW IS 7 FEET 6 INCHES
 OFF OF FINISH FLOOR, WHEREAS SHEET A-6.1.01 DETAIL W1
 THE TOP OF THE WINDOW ELEVATION IS 7FEET 10 ? INCHES.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 4B) PLEASE REVIEW SHEET S-2.00 THE L2 ROOF PLAN
 INDICATES THE USE OF A RBB-1 BEAM. THE TOP OF THE BEAM
 TO BE AT ELEVATION 10 FOOT 6 INCHES. THE BEAM SCHEDULE
 INDICATES THIS BEAM RBB-1 TO BE 1 FOOT 4 INCHES IN
 DEPTH, IN THE COMMENTS IT INDICATES A 16 INCH BOND BEAM
 NO STIRRUPS. OVER THE WINDOW AND DOOR OPENINGS AGAIN
 THE BEAM DESIGNATION OF RBB-1 NO STIRRUPS? IT WOULD
 APPEAR THIS IS A MISTAKE? IT ALSO APPEARS THERE IS A
 NEED OF A LINTEL TO FILE IN THE APPROXIMATE 14 INCH
 VERTICAL GAP? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED? LINTEL SCHEDULE FOUND ON S1.00 BUT NO MENTION
 OF LINTELS ON SHEET S-2.00.
  
 4C) SHEET S-2.00 CMU WALL SCHEDULE MARK MW-1 INDICATES
 THE VERTICAL STEEL EVERY 4 FEET ON CENTER, THE SCHEDULE
 NOR THE DETAIL INDICATE IF CORNER CELLS ARE TO BE FILED
 OR MASONRY CELLS NEXT TO WALL OPENINGS REQUIRE VERTICAL
 REINFORCEMENT AND CELLS FILED? STEEL REINFORCEMENT
 CONFORMING TO ACI 318.
  
 4D) L1 THE GROUND FLOOR PLAN SHOWS TO COLUMNS C1 TO BE
 A 18 X 18 INCH COLUMN AND THE FOUNDATION SCHEDULE
 INDICATES THE MARK AS TE-1 AND THE WIDTH OF THE
 FOUNDATION IS ONLY 16 INCHES WIDE? THE COLUMN IS WIDER
 THAN THE FOUNDATION. 1901.2 REINFORCED CONCRETE.
 STRUCTURAL CONCRETE SHALL BE DESIGNED AND CONSTRUCTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF THIS CHAPTER AND
 ACI 318.
  
 SHEET S-2.00 THE COMPONENTS AND CLADDING PRESSURES ARE
 IN VULT, PLEASE CONVERT TO VASD SINCE ALL OF THE
 PRODUCT APPROVALS ARE IN VASD. 2014 FBC-B 1609.3.1 WIND
 SPEED CONVERSION VULT TO VASD.
  
 5) SHEET A-2.1.01 AND A-6.1.01 BOTH INDICATE THE USE OF
 A LOUVERED SHUTTER BUT NO PRODUCT APPROVAL HAS BEEN
 SUBMITTED. THE PLANS DO NOT STATE IF THIS LOUVER HAS TO
 BE LOWERED IN HIGH WIND EVENTS AND IF THE SHUTTER/
 LOUVER WAS TESTED IN THE OPEN POSITION?
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (C) WALL LOUVERS
 (E) SHUTTERS
  
 6) THE SUBMITTED ROOFING APPROVAL ENTEGRA PLANTATION
 ROOF TILE, MIAMI-DADE NOA 15-0721.04 NEITHER THE
 CONTRACTOR NOR THE DESIGNER OF RECORD HAS INDICATED THE
 TYPE OF FASTENING SYSTEM FOR THIS PRODUCT, TO RESIST
 THE MOMENT OF OVERTURNING, IF NAIL, SCREW, OR FOAM. IF
 FOAM IS TO BE USED PLEASE ALSO SUPPLY THE PRODUCT
 APPROVAL FOR THE UNDERLAYMENT AND FOR THE FOAM.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 7) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved