2017-11-13 15:48:212014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17110020
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. THE BRISTOL
 CONT: SUFFOLK
 TEL: 561-827-3678
 E-MAIL: NMANN@SUFFOLK
  
 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. NOV. 13/ 2017
 ACTION: DENIED
  
 1) PLEASE BE AWARE TO PASS THE SUBMITTED TESTING THERE
 IS (3) COMPONENTS OR CODE SECTIONS THAT NEED TO BE
 SATISFIED.
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) THE CODE INDICATES THAT YOU CAN FIELD TEST UNDER THE
 CODE SECTION 2010 FBC-B 1207.2 FOR AIR BORNE SOUND AND
 TO 1207.3 FOR STRUCTURE- BORNE SOUND. WHAT THE CODE
 DOES NOT PROVIDE IS THE ALTERNATE ASTM FOR BOTH OF THE
 REQUIRED FIELD TEST. TO SUBMIT BOTH OF THE FIELD TESTS
 THE IIC RATING AND STC RATING YOU WILL BE REQUIRED TO
 SUBMIT UNDER THE ALTERNATE MATERIALS, DESIGN AND
 METHODS. A WRITTEN REQUEST TO THE BUILDING OFFICIAL
 ROBERT BROWN MUST BE MADE.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 104.11
 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT.
 THE PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT
 THE INSTALLATION OF ANY MATERIAL OR TO PROHIBIT
 ANY DESIGN OR METHOD OF CONSTRUCTION NOT SPECIFICALLY
 PRESCRIBED BY THIS CODE, PROVIDED THAT ANY SUCH
 ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL BE APPROVED
 WHERE THE BUILDING OFFICIAL FINDS THAT THE PROPOSED
 DESIGN IS SATISFACTORY AND COMPLIES WITH THE INTENT OF
 THE PROVISIONS OF THIS CODE, AND THAT THE MATERIAL,
 METHOD OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE LIFE SAFETY
 SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE TO
 PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND DESIGN
 OF BUILDINGS, OR OTHER METHODS APPROVED BY THE BUILDING
 OFFICIAL MAY BE USED. THE BUILDING OFFICIAL SHALL
 REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE SUBMITTED
 TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE
 ALTERNATIVE.
  
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR
 ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE,
 SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED
 SOURCES.
  
 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE
 OF COMPLIANCE WITH THE PROVISIONS OF THIS CODE, OR
 EVIDENCE THAT A MATERIAL OR METHOD DOES NOT CONFORM TO
 THE REQUIREMENTS OF THIS CODE, OR IN ORDER TO
 SUBSTANTIATE CLAIMS FOR ALTERNATIVE MATERIALS OR
 METHODS, THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY
 TO REQUIRE TESTS AS EVIDENCE OF COMPLIANCE TO BE MADE
 AT NO EXPENSE TO THE JURISDICTION. TEST METHODS SHALL
 BE AS SPECIFIED IN THIS CODE OR BY OTHER RECOGNIZED
 TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED AND
 ACCEPTED TEST METHODS, THE BUILDING OFFICIAL SHALL
 APPROVE THE TESTING PROCEDURES. TESTS SHALL BE
 PERFORMED BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS
 SHALL BE RETAINED BY THE BUILDING OFFICIAL FOR THE
 PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS.
  
 3) IN THIS SUBMITTAL ONLY ONE OF THE REQUIRED 3 TEST
 HAS BEEN SUBMITTED. MISSING ARE THE STC OR SOUND
 TRANSMISSION TEST AND FLAME SPREAD TEST LISTED ABOVE IN
 COMMENTS 1B & 1C.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  