Plan Review Notes
Plan Review Notes For Permit 17110003
Permit Number 17110003
Review Stop P
Sequence Number 2
Notes
Date Text
2018-01-17 17:07:231ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED:
  
 1. PREVIOUS COMMENT #1 IN THE TITLE BLOCK ON THE PLAN
 IT SHOWS THE ADDRESS AS 2600 MILITARY TRAIL, PER THE
 PERMIT THE ADDRESS SHOULD BE 2331 NORTHWOOD UNIVERSITY
 DRIVE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 NEW
 COMMENT THE ADDRESS ON COVER SHEET AND MULTIPLE PLAN
 SEETS WAS CHANGED TO 2331 MILITARY TRAIL WPB THIS
 ADDRESS IS INCORRECT THE CORRECT ADDRESS SHALL BE 2331
 NORTHWOOD UNIVERSITY DR WPB
  
 2. PREVIOUS COMMENT #7 (C) 608.2.1 TRANSFER TYPE SHOWER
 COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED. NEW SHT. A.4.1 SHOWS DIMENSION OF 38" PLEASE
 CORRECT TRANSFER TYPE SHOWERS SHALL BE 36" X 36" INSIDE
 FINISH
  
 3. PREVIOUS COMMENTS #7 ( G) 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 21/2 INCHES
 (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM)
 MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT
 WALL. THE REAR EDGE OF THE "L" PORTION OF THE SEAT
 SHALL BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND
 THE FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND
 15 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF
 THE ?L? SHALL BE 22 INCHES (560 MM) MINIMUM AND 23
 INCHES MAXIMUM (585 MM) FROM THE MAIN SEAT WALL. NEW
 NOT SHOWN ON TRANSFER TYPE SHOWER DETAIL.
  
 4. PREVIOUS COMMENT #9 SHT. A4.6 DETAIL , TYPICAL ADA
 TOILET STALL THE DIMENSION OF THE WC OFF SIDE WALL
 SHALL BE 16? MIN AND 18? MAX, THE DIMENSION SHOWN
 17"MIN 19"MAX IS FOR AMBULATORY STALLS ONLY. PER FBC
 ACC 604.2 NEW DETAIL STILL SHOWS A DIMENSION OF 17" -
 19"
  
 5. PREVIOUS COMMENT #21 ALL DRY VENTS SHALL COMPLY WITH
 FBC PL
 A) 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 B) 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
 NEW ALL DRY VENTS SHALL CONNECT TO THE TOP OF
 HORIZONTAL DRAIN AND SHALL RISE VERTICALLY ABOVE FLOOD
 LEVEL RIM OF FIXTURE IF THE DRY VENT DOES NOT RUN UP
 DIRECTLY INTO A WALL IT WILL BE EXPOSED ABOVE THE SLAB.
 THIS COMMENT IS REFERRING TO THE DRY VENTS ON THE
 CIRCUIT VENT FOR THE WC AND SH IN RM 114, 117, 122
  
 NEW COMMENTS:
  
 1. PROVIDE ISOMETRIC FOR STORM DRAIN. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 2. SHOW THE SLOPE OF THE HORIZONTAL STORM PIPING. PER
 FBC PL 1106.3
  
 3. THE UF FAUCET FOR THE PHYSICAL THERAPY TUB SHALL
 HAVE A WATER TEMPERATURE LIMITING DEVISE PER FBC PL
 424.5 BATHTUB AND WHIRLPOOL BATHTUB VALVES.
 THE HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL
 BATHTUBS SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF
 120?F (49?C) BY A WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE
 SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION 424.3.
  
 4. PLEASE PROVIDE MANUFACTURE SPEC AND INSTALLATION
 GUIDE FOR LINT INTERCEPTOR. PER WPB AMEND TO FBC
 107.2.1
  
 5. PLEASE LABEL HOT RETURN AND COLD PIPING ALONG THE
 RUN ON THE WATER ISOMETRIC. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved