Plan Review Notes
Plan Review Notes For Permit 17110003
Permit Number 17110003
Review Stop P
Sequence Number 1
Notes
Date Text
2017-11-29 13:50:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: TO EXPEDITE APPROVAL I SUGGEST A
 MEETING TO GO OVER COMMENTS.
  
 1. IN THE TITLE BLOCK ON THE PLAN IT SHOWS THE ADDRESS
 AS 2600 MILITARY TRAIL, PER THE PERMIT THE ADDRESS
 SHOULD BE 2331 NORTHWOOD UNIVERSITY DRIVE PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. A2.0 FOR THE PLUMBING FIXTURE COUNT IN THE
 PUBLIC STADIUM BATHROOMS FOR THE REQUIRED WOMEN?S WC IT
 SHALL BE 8. PER FBC PL TABLE 403.1
  
 3. SHT. A2.0 THE FAMILY BATHROOM CAN ONLY BE USED IN
 THE FIXTURE COUNT FOR 1 SEX EITHER MEN?S OR WOMEN?S NOT
 BOTH. PER FBC PL 403.1.2
  
 4. IN BATHROOMS 121 AND 118 A MIN OF ONE OF THE WC
 STALLS SHALL BE AMBULATORY PER FBC ACC 213.3.1 AND
 SHALL COMPLY WITH FBC ACC 604.8.2
  
 5. THE SINK IN THE REFRESHMENT TABLE SHALL COMPLY WITH
 FBC ACC 606 PLEASE SHOW COMPLIANCE WITH FBC ACC 606.3
  
 6. SHT. A4.3 DETAILS J PLEASE CLARIFY THE DIMENSION OF
 3?-5?. PER WPB AMEND TO FBC 107.2.1
  
 7. PLEAS SHOW COMPLIANCE WITH FBC ACC
  
 A) 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 B) 608.5.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE
 SEAT 27 INCHES (685 MM) MAXIMUM FROM THE SIDE WALL
 BEHIND THE SEAT OR SHALL BE LOCATED ON THE BACK WALL
 OPPOSITE THE SEAT 15 INCHES (380 MM) MAXIMUM, LEFT OR
 RIGHT, OF THE CENTERLINE OF THE SEAT. WHERE A SEAT IS
 NOT PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE SIDE WALL FARTHEST FROM
 THE COMPARTMENT ENTRY.
  
 C) 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
  
 D) 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 36
 INCHES (915 MM) WIDE AND 60 INCHES (1525 MM) DEEP
 MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES. A 36 INCH (915 MM) WIDE
 MINIMUM ENTRY SHALL BE PROVIDED AT ONE END OF THE LONG
 SIDE OF THE COMPARTMENT.
  
 E) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
  
 F) 608.3.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE
 WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS
 SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL
 BE INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT
 WALLS.
  
 G) 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 21/2 INCHES
 (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM)
 MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT
 WALL. THE REAR EDGE OF THE ?L? PORTION OF THE SEAT
 SHALL BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND
 THE FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND
 15 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF
 THE ?L? SHALL BE 22 INCHES (560 MM) MINIMUM AND 23
 INCHES MAXIMUM (585 MM) FROM THE MAIN SEAT WALL.
  
 H) 610.3.1 RECTANGULAR SEATS.
 THE REAR EDGE OF A RECTANGULAR SEAT SHALL BE 21/2
 INCHES (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES
 (380 MM) MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM
 THE SEAT WALL. THE SIDE EDGE OF THE SEAT SHALL BE 11/2
 INCHES (38 MM) MAXIMUM FROM THE ADJACENT WALL.
  
  
 8. PLEASE PROVIDE A SCHEDULE FOR SHTS. A4.4, A4.5, A9.0
 LISTING THE LOCATIONS FROM THE LETTERS THAT THE DETAILS
 ARE LABELED WITH. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. A4.6 DETAIL , TYPICAL ADA TOILET STALL THE
 DIMENSION OF THE WC OFF SIDE WALL SHALL BE 16? MIN AND
 18? MAX, THE DIMENSION SHOWN 17?MIN 19?MAX IS FOR
 AMBULATORY STALLS ONLY. PER FBC ACC 604.2
  
 10. SHT. A6.0 THE ROOF DRAIN CALCULATIONS SHOW AREA A
 ONLY PLEASE SHOW THE REST OF THE ROOF. PER WPB AMEND TO
 FBC 107.2.1
  
 11. SHT. P-2.2 SHOWS SQFT OF AREA A AS 3890 THE
 CALCULATION ON SHT A6.0 LIST THE TOTALS AT 4092 PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 12. SHT. P2.2 PLEASE LABEL EMERGENCY SCUPPER DRAINS.
 PER WPB AMEND TO FBC 107.2.1
  
 13. SHTS. P-2.3 AND WS-1 PLEASE PLACE NOTE ON PLAN. A
 SEPARATE PERMIT WITH MANUFACTURE SPECIFICATIONS IS
 REQUIRED FOR THE BACKFLOWS ON DOMESTIC WATER AND FIRE
 LINE. PER WPB UTILITIES DEPT.
  
 14. THE LAVATORY?S SHALL BE LIMITED TO TEMPERED WATER
 ONLY, BY A TEMPERATURE LIMITING DEVISE THAT CONFORMS TO
 ASSE 1070 THE TWO LEONARD MIXING VALVES LISTED IN THE
 EQUIPMENT SCHEDULE, CONFORM TO ASSE 1017 ONLY. THE
 WATTS LFUSG-B-M2 LISTED AS A TEMPERING VALVE UNDER THE
 MISCELLANEOUS PLUMBING SCHEDULE COMPLIES WITH ASSE 1070
 AND FBC PL 416.5 PLEASE SHOW VALVES INSTALLED ON
 ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1
  
 15. PLEASE SHOW TRAP PRIMERS ON ALL FLOOR DRAINS ON THE
 ISOMETRIC DRAWINGS. PER FBC PL 1002.4
  
 16. SHT. P-4 THE KITCHEN SINK IN THE STORAGE ROOM IS
 LABELED HS ON THE ISOMETRIC DRAWING PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 17. THE FLOOR SINK FOR THE ICE MACHINE IS NOT VENTED IT
 SHALL COMPLY WITH FBC PL 901.2.1
  
 18. PLEASE CLEARLY LABEL ICE MACHINE ON THE PLUMBING
 FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1
  
 19. A BACKFLOW IS REQUIRED ON WATER SUPPLY FOR THE ICE
 MACHINE. PER FBC PL 608.3
  
 20. WHAT IS THE UF IN THE PHYSICAL THERAPY ROOM BEING
 USED FOR PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 21. ALL DRY VENTS SHALL COMPLY WITH FBC PL
  
 A) 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
  
 B) 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
  
 22. SHT. P-4 THE DRY VENT AT THE END OF THE BRANCH
 DRAIN FOR THE FLOOR DRAINS IN THE WEIGHT ROOM, THE DRY
 VENT AT THE END OF THE BRANCH DRAIN FOR PHYSICAL
 THERAPY ROOM, THE DRY VENT AT THE END OF THE BRANCH
 DRAIN FOR THE GANG SHOWERS AND THE DRY VENT IN THE
 MIDDLE OF THE BRANCH DRAIN FOR THE GANG WC IN THE
 WOMEN?S STADIUM BATHROOM DO NOT COMPLY WITH FBC PL
 905.3 AND 905.4 AND SHALL BE REMOVED FROM PLAN AND CODE
 COMPLIANT DRY VENTS ADDED IN PROPER LOCATIONS.
  
 23. THE CIRCUIT VENTS SHALL COMPLY WITH FBC PL
  
 A) 914.1 CIRCUIT VENT PERMITTED.
 A MAXIMUM OF EIGHT FIXTURES CONNECTED TO A HORIZONTAL
 BRANCH DRAIN SHALL BE PERMITTED TO BE CIRCUIT VENTED.
 EACH FIXTURE DRAIN SHALL CONNECT HORIZONTALLY TO THE
 HORIZONTAL BRANCH BEING CIRCUIT VENTED. THE HORIZONTAL
 BRANCH DRAIN SHALL BE CLASSIFIED AS A VENT FROM THE
 MOST DOWNSTREAM FIXTURE DRAIN CONNECTION TO THE MOST
 UPSTREAM FIXTURE DRAIN CONNECTION TO THE HORIZONTAL
 BRANCH.
  
 B) 914.1.1 MULTIPLE CIRCUIT-VENTED BRANCHES.
 CIRCUIT-VENTED HORIZONTAL BRANCH DRAINS ARE PERMITTED
 TO BE CONNECTED TOGETHER. EACH GROUP OF A MAXIMUM OF
 EIGHT FIXTURES SHALL BE CONSIDERED A SEPARATE CIRCUIT
 VENT AND SHALL CONFORM TO THE REQUIREMENTS OF THIS
 SECTION.
  
 C) 914.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
 1) THE CIRCUIT VENT FOR THE GANG SHOWERS SHALL HAVE A
 DRY VENT LOCATED BETWEEN THE 1ST AND 2ND MOST UPSTREAM
 SHOWERS AND 5TH AND 6TH SHOWERS.
 2) THE CIRCUIT VENT FOR THE GANG WC IN THE STUDENT
 ATHLETE BATHROOMS SHALL HAVE A DRY VENT LOCATED BETWEEN
 THE 1ST AND 2ND WC AND THE 5TH AND 6TH WC.
 3) THE CIRCUIT VENT FOR THE GANG WC IN THE WOMEN?S
 STADIUM BATHROOM SHALL HAVE A DRY VENT LOCATED BETWEEN
 THE 1ST AND 2ND MOST UPSTREAM WC.
  
 24. THE WC IN THE WOMEN?S STADIUM BATHROOM ACROSS FROM
 THE ACCESSIBLE STALL IS NOT VENTED PROPERLY IT SHALL
 COMPLY WITH FBC PL
  
 A) 901.2 TRAP SEAL PROTECTION.
 THE PLUMBING SYSTEM SHALL BE PROVIDED WITH A SYSTEM OF
 VENT PIPING THAT WILL PERMIT THE ADMISSION OR EMISSION
 OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP SHALL NOT
 BE SUBJECTED TO A PNEUMATIC PRESSURE DIFFERENTIAL OF
 MORE THAN 1 INCH OF WATER COLUMN (249 PA).
 B) 901.2.1 VENTING REQUIRED.
 TRAPS AND TRAPPED FIXTURES SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
  
  
 25. A WATER-HAMMER ARRESTOR IS REQUIRED ON THE ICE
 MACHINE AND THE WATER FOUNTAINS. PER FBC PL 604.9
  
 26. THE WATER SUPPLY FOR THE WATER FOUNTAIN LOCATED
 OUTSIDE STADIUM BATHROOMS IS MISSING FROM THE ISOMETRIC
 DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 27. SHUT OFF VALVES ARE REQUIRED AT THE HOSE BIBS
 PLEASE SHOW ON WATER ISOMETRIC DRAWING. PER FBC PL
 606.2(2)
  
 28. SHUT OFF VALVES ARE REQUIRED ON THE DROPS TO THE
 SHOWER VALVES. PER FBC PL 606.1(5)
  
 29. SHT. P-2.3 WHAT IS THE B+G CIRCUIT SETTER W/BALL
 VALVE SHOWN ON THE WATER FLOOR PLAN PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 30. PLEASE SIZE THE WATER STUB OUTS ON THE ISOMETRIC
 DRAWING FOR THE WC + UR. PER WPB AMEND TO FBC 107.2.1
  
 31. A LINT TRAP IS REQUIRED FOR THE WASHING MACHINE
 DRAIN. PER FBC PL 1003.6 LAUNDRIES.
 LAUNDRY FACILITIES NOT INSTALLED WITHIN AN INDIVIDUAL
 DWELLING UNIT OR INTENDED FOR INDIVIDUAL FAMILY USE
 SHALL BE EQUIPPED WITH AN INTERCEPTOR WITH A WIRE
 BASKET OR SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT
 PREVENTS PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2
 INCH (12.7 MM) OR LARGER IN SIZE, STRING, RAGS, BUTTONS
 OR OTHER MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE
 SYSTEM.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  