| 2017-11-29 13:50:18 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: TO EXPEDITE APPROVAL I SUGGEST A |
| | MEETING TO GO OVER COMMENTS. |
| | |
| | 1. IN THE TITLE BLOCK ON THE PLAN IT SHOWS THE ADDRESS |
| | AS 2600 MILITARY TRAIL, PER THE PERMIT THE ADDRESS |
| | SHOULD BE 2331 NORTHWOOD UNIVERSITY DRIVE PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. A2.0 FOR THE PLUMBING FIXTURE COUNT IN THE |
| | PUBLIC STADIUM BATHROOMS FOR THE REQUIRED WOMEN?S WC IT |
| | SHALL BE 8. PER FBC PL TABLE 403.1 |
| | |
| | 3. SHT. A2.0 THE FAMILY BATHROOM CAN ONLY BE USED IN |
| | THE FIXTURE COUNT FOR 1 SEX EITHER MEN?S OR WOMEN?S NOT |
| | BOTH. PER FBC PL 403.1.2 |
| | |
| | 4. IN BATHROOMS 121 AND 118 A MIN OF ONE OF THE WC |
| | STALLS SHALL BE AMBULATORY PER FBC ACC 213.3.1 AND |
| | SHALL COMPLY WITH FBC ACC 604.8.2 |
| | |
| | 5. THE SINK IN THE REFRESHMENT TABLE SHALL COMPLY WITH |
| | FBC ACC 606 PLEASE SHOW COMPLIANCE WITH FBC ACC 606.3 |
| | |
| | 6. SHT. A4.3 DETAILS J PLEASE CLARIFY THE DIMENSION OF |
| | 3?-5?. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. PLEAS SHOW COMPLIANCE WITH FBC ACC |
| | |
| | A) 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS, |
| | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON |
| | THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM) |
| | MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE |
| | SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL |
| | 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE |
| | SEAT TOWARD THE SHOWER OPENING. |
| | |
| | B) 608.5.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS. |
| | IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE |
| | CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| | LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 |
| | INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT |
| | IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY |
| | UNIT SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE |
| | SEAT 27 INCHES (685 MM) MAXIMUM FROM THE SIDE WALL |
| | BEHIND THE SEAT OR SHALL BE LOCATED ON THE BACK WALL |
| | OPPOSITE THE SEAT 15 INCHES (380 MM) MAXIMUM, LEFT OR |
| | RIGHT, OF THE CENTERLINE OF THE SEAT. WHERE A SEAT IS |
| | NOT PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY |
| | UNIT SHALL BE INSTALLED ON THE SIDE WALL FARTHEST FROM |
| | THE COMPARTMENT ENTRY. |
| | |
| | C) 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES |
| | (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS |
| | MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND |
| | SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE |
| | FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES |
| | (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG |
| | MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE |
| | PROVIDED. |
| | |
| | D) 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS. |
| | ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 36 |
| | INCHES (915 MM) WIDE AND 60 INCHES (1525 MM) DEEP |
| | MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER |
| | POINTS OF OPPOSING SIDES. A 36 INCH (915 MM) WIDE |
| | MINIMUM ENTRY SHALL BE PROVIDED AT ONE END OF THE LONG |
| | SIDE OF THE COMPARTMENT. |
| | |
| | E) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE |
| | PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A |
| | POINT 18 INCHES (455 MM) FROM THE CONTROL WALL. |
| | |
| | F) 608.3.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS. |
| | IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB |
| | BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE |
| | WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS |
| | SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL |
| | BE INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT |
| | WALLS. |
| | |
| | G) 610.3.2 L-SHAPED SEATS. |
| | THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 21/2 INCHES |
| | (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM) |
| | MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT |
| | WALL. THE REAR EDGE OF THE ?L? PORTION OF THE SEAT |
| | SHALL BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND |
| | THE FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND |
| | 15 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF |
| | THE ?L? SHALL BE 22 INCHES (560 MM) MINIMUM AND 23 |
| | INCHES MAXIMUM (585 MM) FROM THE MAIN SEAT WALL. |
| | |
| | H) 610.3.1 RECTANGULAR SEATS. |
| | THE REAR EDGE OF A RECTANGULAR SEAT SHALL BE 21/2 |
| | INCHES (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES |
| | (380 MM) MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM |
| | THE SEAT WALL. THE SIDE EDGE OF THE SEAT SHALL BE 11/2 |
| | INCHES (38 MM) MAXIMUM FROM THE ADJACENT WALL. |
| | |
| | |
| | 8. PLEASE PROVIDE A SCHEDULE FOR SHTS. A4.4, A4.5, A9.0 |
| | LISTING THE LOCATIONS FROM THE LETTERS THAT THE DETAILS |
| | ARE LABELED WITH. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. SHT. A4.6 DETAIL , TYPICAL ADA TOILET STALL THE |
| | DIMENSION OF THE WC OFF SIDE WALL SHALL BE 16? MIN AND |
| | 18? MAX, THE DIMENSION SHOWN 17?MIN 19?MAX IS FOR |
| | AMBULATORY STALLS ONLY. PER FBC ACC 604.2 |
| | |
| | 10. SHT. A6.0 THE ROOF DRAIN CALCULATIONS SHOW AREA A |
| | ONLY PLEASE SHOW THE REST OF THE ROOF. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 11. SHT. P-2.2 SHOWS SQFT OF AREA A AS 3890 THE |
| | CALCULATION ON SHT A6.0 LIST THE TOTALS AT 4092 PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 12. SHT. P2.2 PLEASE LABEL EMERGENCY SCUPPER DRAINS. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 13. SHTS. P-2.3 AND WS-1 PLEASE PLACE NOTE ON PLAN. A |
| | SEPARATE PERMIT WITH MANUFACTURE SPECIFICATIONS IS |
| | REQUIRED FOR THE BACKFLOWS ON DOMESTIC WATER AND FIRE |
| | LINE. PER WPB UTILITIES DEPT. |
| | |
| | 14. THE LAVATORY?S SHALL BE LIMITED TO TEMPERED WATER |
| | ONLY, BY A TEMPERATURE LIMITING DEVISE THAT CONFORMS TO |
| | ASSE 1070 THE TWO LEONARD MIXING VALVES LISTED IN THE |
| | EQUIPMENT SCHEDULE, CONFORM TO ASSE 1017 ONLY. THE |
| | WATTS LFUSG-B-M2 LISTED AS A TEMPERING VALVE UNDER THE |
| | MISCELLANEOUS PLUMBING SCHEDULE COMPLIES WITH ASSE 1070 |
| | AND FBC PL 416.5 PLEASE SHOW VALVES INSTALLED ON |
| | ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 15. PLEASE SHOW TRAP PRIMERS ON ALL FLOOR DRAINS ON THE |
| | ISOMETRIC DRAWINGS. PER FBC PL 1002.4 |
| | |
| | 16. SHT. P-4 THE KITCHEN SINK IN THE STORAGE ROOM IS |
| | LABELED HS ON THE ISOMETRIC DRAWING PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 17. THE FLOOR SINK FOR THE ICE MACHINE IS NOT VENTED IT |
| | SHALL COMPLY WITH FBC PL 901.2.1 |
| | |
| | 18. PLEASE CLEARLY LABEL ICE MACHINE ON THE PLUMBING |
| | FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 19. A BACKFLOW IS REQUIRED ON WATER SUPPLY FOR THE ICE |
| | MACHINE. PER FBC PL 608.3 |
| | |
| | 20. WHAT IS THE UF IN THE PHYSICAL THERAPY ROOM BEING |
| | USED FOR PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 21. ALL DRY VENTS SHALL COMPLY WITH FBC PL |
| | |
| | A) 905.3 VENT CONNECTION TO DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | |
| | B) 905.4 VERTICAL RISE OF VENT. |
| | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT |
| | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM |
| | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | |
| | |
| | 22. SHT. P-4 THE DRY VENT AT THE END OF THE BRANCH |
| | DRAIN FOR THE FLOOR DRAINS IN THE WEIGHT ROOM, THE DRY |
| | VENT AT THE END OF THE BRANCH DRAIN FOR PHYSICAL |
| | THERAPY ROOM, THE DRY VENT AT THE END OF THE BRANCH |
| | DRAIN FOR THE GANG SHOWERS AND THE DRY VENT IN THE |
| | MIDDLE OF THE BRANCH DRAIN FOR THE GANG WC IN THE |
| | WOMEN?S STADIUM BATHROOM DO NOT COMPLY WITH FBC PL |
| | 905.3 AND 905.4 AND SHALL BE REMOVED FROM PLAN AND CODE |
| | COMPLIANT DRY VENTS ADDED IN PROPER LOCATIONS. |
| | |
| | 23. THE CIRCUIT VENTS SHALL COMPLY WITH FBC PL |
| | |
| | A) 914.1 CIRCUIT VENT PERMITTED. |
| | A MAXIMUM OF EIGHT FIXTURES CONNECTED TO A HORIZONTAL |
| | BRANCH DRAIN SHALL BE PERMITTED TO BE CIRCUIT VENTED. |
| | EACH FIXTURE DRAIN SHALL CONNECT HORIZONTALLY TO THE |
| | HORIZONTAL BRANCH BEING CIRCUIT VENTED. THE HORIZONTAL |
| | BRANCH DRAIN SHALL BE CLASSIFIED AS A VENT FROM THE |
| | MOST DOWNSTREAM FIXTURE DRAIN CONNECTION TO THE MOST |
| | UPSTREAM FIXTURE DRAIN CONNECTION TO THE HORIZONTAL |
| | BRANCH. |
| | |
| | B) 914.1.1 MULTIPLE CIRCUIT-VENTED BRANCHES. |
| | CIRCUIT-VENTED HORIZONTAL BRANCH DRAINS ARE PERMITTED |
| | TO BE CONNECTED TOGETHER. EACH GROUP OF A MAXIMUM OF |
| | EIGHT FIXTURES SHALL BE CONSIDERED A SEPARATE CIRCUIT |
| | VENT AND SHALL CONFORM TO THE REQUIREMENTS OF THIS |
| | SECTION. |
| | |
| | C) 914.2 VENT CONNECTION. |
| | THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| | THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED |
| | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE |
| | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. |
| | |
| | 1) THE CIRCUIT VENT FOR THE GANG SHOWERS SHALL HAVE A |
| | DRY VENT LOCATED BETWEEN THE 1ST AND 2ND MOST UPSTREAM |
| | SHOWERS AND 5TH AND 6TH SHOWERS. |
| | 2) THE CIRCUIT VENT FOR THE GANG WC IN THE STUDENT |
| | ATHLETE BATHROOMS SHALL HAVE A DRY VENT LOCATED BETWEEN |
| | THE 1ST AND 2ND WC AND THE 5TH AND 6TH WC. |
| | 3) THE CIRCUIT VENT FOR THE GANG WC IN THE WOMEN?S |
| | STADIUM BATHROOM SHALL HAVE A DRY VENT LOCATED BETWEEN |
| | THE 1ST AND 2ND MOST UPSTREAM WC. |
| | |
| | 24. THE WC IN THE WOMEN?S STADIUM BATHROOM ACROSS FROM |
| | THE ACCESSIBLE STALL IS NOT VENTED PROPERLY IT SHALL |
| | COMPLY WITH FBC PL |
| | |
| | A) 901.2 TRAP SEAL PROTECTION. |
| | THE PLUMBING SYSTEM SHALL BE PROVIDED WITH A SYSTEM OF |
| | VENT PIPING THAT WILL PERMIT THE ADMISSION OR EMISSION |
| | OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP SHALL NOT |
| | BE SUBJECTED TO A PNEUMATIC PRESSURE DIFFERENTIAL OF |
| | MORE THAN 1 INCH OF WATER COLUMN (249 PA). |
| | B) 901.2.1 VENTING REQUIRED. |
| | TRAPS AND TRAPPED FIXTURES SHALL BE VENTED IN |
| | ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| | THIS CHAPTER. |
| | |
| | |
| | 25. A WATER-HAMMER ARRESTOR IS REQUIRED ON THE ICE |
| | MACHINE AND THE WATER FOUNTAINS. PER FBC PL 604.9 |
| | |
| | 26. THE WATER SUPPLY FOR THE WATER FOUNTAIN LOCATED |
| | OUTSIDE STADIUM BATHROOMS IS MISSING FROM THE ISOMETRIC |
| | DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 27. SHUT OFF VALVES ARE REQUIRED AT THE HOSE BIBS |
| | PLEASE SHOW ON WATER ISOMETRIC DRAWING. PER FBC PL |
| | 606.2(2) |
| | |
| | 28. SHUT OFF VALVES ARE REQUIRED ON THE DROPS TO THE |
| | SHOWER VALVES. PER FBC PL 606.1(5) |
| | |
| | 29. SHT. P-2.3 WHAT IS THE B+G CIRCUIT SETTER W/BALL |
| | VALVE SHOWN ON THE WATER FLOOR PLAN PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 30. PLEASE SIZE THE WATER STUB OUTS ON THE ISOMETRIC |
| | DRAWING FOR THE WC + UR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 31. A LINT TRAP IS REQUIRED FOR THE WASHING MACHINE |
| | DRAIN. PER FBC PL 1003.6 LAUNDRIES. |
| | LAUNDRY FACILITIES NOT INSTALLED WITHIN AN INDIVIDUAL |
| | DWELLING UNIT OR INTENDED FOR INDIVIDUAL FAMILY USE |
| | SHALL BE EQUIPPED WITH AN INTERCEPTOR WITH A WIRE |
| | BASKET OR SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT |
| | PREVENTS PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2 |
| | INCH (12.7 MM) OR LARGER IN SIZE, STRING, RAGS, BUTTONS |
| | OR OTHER MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE |
| | SYSTEM. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |