2017-11-28 15:58:551ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17110003
 11/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-1.1 & M-2.1: THE EXHAUST CALCULATIONS ARE
 INDICATING 1940 CFMS OF EXHAUST PROVIDED FOR THE
 LOCKER/RESTROOMS/SHOWERS FOR BOTH RTU-3 & 4, HOWEVER
 THE FLOOR PLAN DRAWING IS INDICATING 2540 CFMS OF
 EXHAUST FROM THE LOCKERS/SHOWERS/RESTROOMS FOR EACH OF
 THE SYSTEMS, AND AN ADDITIONAL 350 CFMS OF
 RETURN/EXHAUST FROM THE OFFICES FOR EACH SYSTEM. BEING
 THAT THE
  
 ERV'S HAVE CAPACITIES OF 1940 CMS, IT APPEARS THAT
 RECIRCULATION OF AIR EXCEEDING 10% OF THE SUPPLY AIR
 STREAMS WILL OCCUR- SEE TABLE 403.3 FOOTNOTE G.
  
 2) SHEET M-2.1: INDICATE THE AMOUNT OF MAKEUP AIR BEING
 TRANSFERRED FROM THE CORRIDOR INTO THE LOCKER ROOMS-
 REFER TO SECTION 601.2.
  
 3) PLEASE PROVIDE MORE INFORMTION ABOUT THE LAUNDRY
 ROOM IN COMPLIANCE WITH SECTION 504. A) INDICATE THE
 NUMBER OF DRYERS IN THE ROOM AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS. B) CLARIFY IF THE 8" EXHAUST DUCT IS A
 COMMON EXHAUST DUCT FOR MULTIPLE DRYERS, AND PROVIDE AN
 ELEVATION DRAWING. C) PROVIDE A MAKEUP AIR CALCULATION
 INDICATING WHAT IS REQUIRED AND WHAT WILL BE PROVIDED.
  
 4) PLEASE SEE SHEETS S4.1 & M-3.1. THE DETAILS PROVIDED
 FOR ATTACHING THE RTU'S TO THE CURBS, AND ATTACHING THE
 CURBS TO THE ROOF STRUCTURE DO NOT MATCH. PLEASE
 PROVIDE CONSISTENT ENGINEERED DETAILS THAT ARE
 COMPLIANT WITH SECTION 1609 FBC-14 BUILDING.
  
 5) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE RTU'S.
 PROVIDE TYPES AND SIZES OF PIPING, PIPING RUNS AND
 DISCHARGE LOCATIONS, AND PIPING INSULATION DETAILS-
 SECTION 307.
  
 6) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED
 IN ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY
 CONSERVATION. PROVIDE A COMMISSIONING PLAN IN
 ACCORDANCE WITH SECTION C408.2.1. PLEASE NOTE THAT A
 COMMISSIONING REPORT IS REQUIRED TO PASS THE FINAL
 MECHANICAL INSPECTION- SEE SECTIONS C408.2.4-
 C408.2.5.4.
  
 7) THE ENGINEER OF RECORD ERIC J. SVOBODA P.E. SHALL
 PROVIDE HIS RAISED OR INK SEAL ON THE CERTIFICATIONS
 PAGE OF THE ENERGYGAUGE COMPLIANCE FORM- SEE SECTION
 C103.1.1.1.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  