| 2017-11-28 15:58:55 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17110003 |
| | 11/28/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M-1.1 & M-2.1: THE EXHAUST CALCULATIONS ARE |
| | INDICATING 1940 CFMS OF EXHAUST PROVIDED FOR THE |
| | LOCKER/RESTROOMS/SHOWERS FOR BOTH RTU-3 & 4, HOWEVER |
| | THE FLOOR PLAN DRAWING IS INDICATING 2540 CFMS OF |
| | EXHAUST FROM THE LOCKERS/SHOWERS/RESTROOMS FOR EACH OF |
| | THE SYSTEMS, AND AN ADDITIONAL 350 CFMS OF |
| | RETURN/EXHAUST FROM THE OFFICES FOR EACH SYSTEM. BEING |
| | THAT THE |
| | |
| | ERV'S HAVE CAPACITIES OF 1940 CMS, IT APPEARS THAT |
| | RECIRCULATION OF AIR EXCEEDING 10% OF THE SUPPLY AIR |
| | STREAMS WILL OCCUR- SEE TABLE 403.3 FOOTNOTE G. |
| | |
| | 2) SHEET M-2.1: INDICATE THE AMOUNT OF MAKEUP AIR BEING |
| | TRANSFERRED FROM THE CORRIDOR INTO THE LOCKER ROOMS- |
| | REFER TO SECTION 601.2. |
| | |
| | 3) PLEASE PROVIDE MORE INFORMTION ABOUT THE LAUNDRY |
| | ROOM IN COMPLIANCE WITH SECTION 504. A) INDICATE THE |
| | NUMBER OF DRYERS IN THE ROOM AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS. B) CLARIFY IF THE 8" EXHAUST DUCT IS A |
| | COMMON EXHAUST DUCT FOR MULTIPLE DRYERS, AND PROVIDE AN |
| | ELEVATION DRAWING. C) PROVIDE A MAKEUP AIR CALCULATION |
| | INDICATING WHAT IS REQUIRED AND WHAT WILL BE PROVIDED. |
| | |
| | 4) PLEASE SEE SHEETS S4.1 & M-3.1. THE DETAILS PROVIDED |
| | FOR ATTACHING THE RTU'S TO THE CURBS, AND ATTACHING THE |
| | CURBS TO THE ROOF STRUCTURE DO NOT MATCH. PLEASE |
| | PROVIDE CONSISTENT ENGINEERED DETAILS THAT ARE |
| | COMPLIANT WITH SECTION 1609 FBC-14 BUILDING. |
| | |
| | 5) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE RTU'S. |
| | PROVIDE TYPES AND SIZES OF PIPING, PIPING RUNS AND |
| | DISCHARGE LOCATIONS, AND PIPING INSULATION DETAILS- |
| | SECTION 307. |
| | |
| | 6) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED |
| | IN ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY |
| | CONSERVATION. PROVIDE A COMMISSIONING PLAN IN |
| | ACCORDANCE WITH SECTION C408.2.1. PLEASE NOTE THAT A |
| | COMMISSIONING REPORT IS REQUIRED TO PASS THE FINAL |
| | MECHANICAL INSPECTION- SEE SECTIONS C408.2.4- |
| | C408.2.5.4. |
| | |
| | 7) THE ENGINEER OF RECORD ERIC J. SVOBODA P.E. SHALL |
| | PROVIDE HIS RAISED OR INK SEAL ON THE CERTIFICATIONS |
| | PAGE OF THE ENERGYGAUGE COMPLIANCE FORM- SEE SECTION |
| | C103.1.1.1.2. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |