| 2017-11-29 14:45:29 | 11-29-2017 2ND GAS REVIEW**DENIED** |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 3 OF THE 5 COMMENTS FROM THE 1ST REVIEW HAD NOT BEEN |
| | ADDRESSED |
| | |
| | 1) MSSSING MANUFACTURERS INSTALLATION MANUAL FOR THE |
| | FIRE BOWL. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 |
| | |
| | 2) NO SIZING TABLES SUPPLIED. SUBMIT TWO COPIES OF THE |
| | APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR |
| | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH |
| | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD |
| | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER |
| | TO THE 2014 FBC-FUEL GAS SECS. 401.4, 401.8 THRU |
| | 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR 2014 |
| | FBC-RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, & |
| | G2413.3 |
| | |
| | 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |
| | |