| 2017-11-06 10:24:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. DELEGATED ENGINEERING IS TO BE REVIEWED BY | | | STRUCTURAL ENGINEER OF RECORD PRIOR TO SUBMITTAL, FBC | | | 107. | | | | | | 2. DELEGATED ENGINEER CANNOT REDUCE DESIGN PRESSURES, | | | SEE SHEET S3 PREPARED BY ONM&J. EITHER DELEGATED | | | ENGINEER IS TO REVISE PLAN TO MEET PRESSURES SPECIFIED | | | BY SEOR, OR SEOR IS TO REVISE SHEET S3. | | | | | | 3. A ROOF PRODUCT APPROVAL WAS SUBMITTED. THIS IS TO BE | | | REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, FBC | | | 107. NOTE THAT IT IS PREFERABLE FOR THIS TO BE | | | SUBMITTED WITH THE ROOF PERMIT APPLICATION. AT SOME | | | POINT (PREFERABLY WITH THE PRODUCT APPROVAL SUBMISSION) | | | RAS117 CALCULATIONS PREPARED BY A DESIGN PROFESSIONAL | | | (IF REQUIRED) AND ASSEMBLY PROPOSED IS REQUIRED. THIS | | | CAN BE DONE AT ANY TIME, BUT REQUIRED BEFORE ISSUANCE | | | OF ROOF SUB PERMIT OR COMMENCEMENT OF ANY ROOF | | | (COVERING) WORK. | | | | | | PAGES 13 - 15 OF THE NOA WERE HIGHLIGHTED. THIS | | | INCLUDES TWO DIFFERENT ASSEMBLIES; ARE BOTH PROPOSED? | | | ALSO INDICATE WHICH FASTENING OPTION IS PROPOSED. RAS | | | 117 CALCULATIONS ARE REQUIRED FOR ALL OPTIONS. | | | | | | | | | | | | |
|