| Plan Review Notes For Permit 17101256 |
| Permit Number |
17101256 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-07 15:10:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS INSUFFICIENT DETAIL PROVIDE TO COMPLETE A | | | THOROUGH LIFE SAFETY PALN REVIEW. | | | | | | | | | 2) THERE IS NO ADDRESS AND BUSINESS NAME ON THE TITLE | | | BLOCK OF THE SUBMITTED SHEETS. | | | | | | PLEASE PROVIDE | | | | | | | | | 3) PREVIOUS PERMIT PLANS INDICATE THAT THE BUILDING HAS | | | A COMPLETE FIRE SPRINKLER SYSTEM. | | | | | | ANY WORK THAT REMOVES OR INSTALLS WALLS SHALL HAVE THE | | | FIRE SPRINKLER SYSTEM PROTECTION REVIEWED FOR CODE | | | COMPLIANCE AND SHOP DRAWINGS SUBMITTAL. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF FUTURE SHOP | | | DRAWINGS. | | | | | | | | | 4) PREVIOUS PERMIT PLANS INDICATE THAT THE BUILDING HAS | | | A FIRE ALARM SYSTEM. | | | | | | ANY WORK THAT REMOVES OR INSTALLS WALLS SHALL HAVE THE | | | FIRE ALARMSYSTEM PROTECTION REVIEWED FOR CODE | | | COMPLIANCE AND SHOP DRAWINGS SUBMITTAL. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF FUTURE SHOP | | | DRAWINGS. | | | | | | | | | 5) ANY PROPOSED WORK AFTER THE REMOVAL OF WALLS SHALL | | | REQUIRE A NEW PERMIT. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|