2017-11-07 15:10:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDE TO COMPLETE A
 THOROUGH LIFE SAFETY PALN REVIEW.
  
  
 2) THERE IS NO ADDRESS AND BUSINESS NAME ON THE TITLE
 BLOCK OF THE SUBMITTED SHEETS.
  
 PLEASE PROVIDE
  
  
 3) PREVIOUS PERMIT PLANS INDICATE THAT THE BUILDING HAS
 A COMPLETE FIRE SPRINKLER SYSTEM.
  
 ANY WORK THAT REMOVES OR INSTALLS WALLS SHALL HAVE THE
 FIRE SPRINKLER SYSTEM PROTECTION REVIEWED FOR CODE
 COMPLIANCE AND SHOP DRAWINGS SUBMITTAL.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF FUTURE SHOP
 DRAWINGS.
  
  
 4) PREVIOUS PERMIT PLANS INDICATE THAT THE BUILDING HAS
 A FIRE ALARM SYSTEM.
  
 ANY WORK THAT REMOVES OR INSTALLS WALLS SHALL HAVE THE
 FIRE ALARMSYSTEM PROTECTION REVIEWED FOR CODE
 COMPLIANCE AND SHOP DRAWINGS SUBMITTAL.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF FUTURE SHOP
 DRAWINGS.
  
  
 5) ANY PROPOSED WORK AFTER THE REMOVAL OF WALLS SHALL
 REQUIRE A NEW PERMIT.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  