| Date |
Text |
| 2018-01-10 12:10:43 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| | |
| | 2ND REQUEST 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE |
| | TOILET, URINAL AND LAVATORY. PER FBC ACC 604.3.1, 605.3 |
| | AND 606.2 SHT. A2.1 DOES NOT SHOW THE CLEAR FLOOR SPACE |
| | FOR THE TOILET AND URINAL. |
| | |
| | 2ND REQUEST 2. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALLL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | A) DETAILS #3, #4, #7 SHOWS A DIMENSION OF 6-3/4" FROM |
| | THE TOP OF THE LAVATORY TO THE BOTTOM OF THE MIRROR |
| | WHICH MAKES THE TOTAL DIMENSION FROM FINISHED FLOOR TO |
| | THE BOTTOM OF THE MIRROR 40-3/4" THE CODE REQUIRES 40" |
| | EXACTLY 3/4" IS TO MUCH TO ALLOW FOR A TOLERANCE PLEASE |
| | CORRECT THE DIMENSION SO THAT IT MEETS THE CODE |
| | REQUIREMENT. |
| | B) DETAIL #5 SOMEONE CHANGED THE IN PEN THE MIN 40" TO |
| | MAX ON THE DOUBLE LAVATORY BUT THEY DID NOT CHANGE |
| | IT-ON THE SINGLE LAVATORY IN-THE ACCESSIBLE STALL |
| | |
| | 2ND REQUEST 3. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE. PLEASE SHOW THE GRAB BARS MEASURED TO THE TOP |
| | OF THE GRIPPING SURFACE. |
| | |
| | 2ND REQUEST 4. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. SHOW DIMENSION ON PLAN |
| | |
| | 2ND REQUEST 5. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 604.5.1 SIDE WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| | LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE REAR WALL |
| | AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. |
| | |
| | 2ND REQUEST 6. SHT. A2.1 DETAIL #8 SHOWS LAVATORY RIM |
| | AT 36" OF FINISH FLOOR IT SHALL BE 34". PER FBC ACC |
| | 606.3 |
| | |
| | 2ND REQUEST 10. THE WATER FILTER SHOWN ON SHT. K 2.0 |
| | DETAIL P.1 IS NOT SHOWN ON WATER PIPE RISER PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 EVEN IF IT IS |
| | EXISTING PLEASE SHOW ON WATER AND SANITARY RISER |
| | DIAGRAM AND MARK AS EXISTING. |
| | |
| | 2ND REQUEST 11. A BACKFLOW IS REQUIRED ON SUPPLY TO ICE |
| | MACHINE WATER FILTER AND BEVERAGE DISPENSERS AND COFFEE |
| | MACHINES. PER FBC PL 608.3, 608.16.1 AND 608.16.10 |
| | BACKFLOWS ARE NOT SHOWN ON THE WATER RISER AND ON THE |
| | PLUMBING FIXTURE SCHEDULE IT REFERS TO NOTE 23 I COULD |
| | NOT LOCATE NOTE 23 ON PLAN SHEET. |
| | |
| | 2ND REQUEST 12. ONLY FIXTURES THAT PRODUCE GREASE WASTE |
| | SHALL DISCHARGE THROUGH A GREASE INTERCEPTOR LIKE |
| | KITCHEN AND FOOD PREP AREA AND MOP SIN, THE FIXTURES IN |
| | BAR AREA SHALL NOT DISCHARGE THROUGH THE GREASE |
| | INTERCEPTOR. PER FBC PL 1003.2 THE BARS FIXTURE ARE |
| | STILL SHOWN ON GREASE WASTE RISER. |
| | |
| | 2ND REQUEST 13. LAVATORY'S SHALL COMPLY WITH FBC PL |
| | 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. NOT SHOWN ON PLAN PLEASE PROVIDE |
| | NOTE |
| | |
| | 2ND REQUEST 14. P;LEASE SHOW ICE MACHINE ON WATER |
| | RISER. PER WPB AMEND TO FBC 107.2.1 NOT SHOW ON RISER |
| | EVEN IF IT IS EXISTING PLEASE SHOW ON WATER AND |
| | SANITARY RISER DIAGRAM AND MARK AS EXISTING. |
| | |
| | 2ND REQUEST 15. THE FIXTURE COUNT SHAL COMPLY WITH FBC |
| | PL 403.1.3 POTTY PARITY. |
| | IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO |
| | THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS |
| | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| | CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE |
| | TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH |
| | SECTION 553.86, FLORIDA STATUTES. |
| | IN ORDER TO COMPLY WITH THIS CODE SEC THERE SHALL BE |
| | THE SAME NUMBER OF TOILETS IN THE WOMENS BATHROOM AS |
| | THE COMBINED NUMBERS OF TOILETS AND URINALS IN THE |
| | MENS. |
| | |
| | |
| | 2ND REQUEST 16. A TEST PORT IS REQUIRED ON THE |
| | DISCHARGE OF GREASE INTERCEPTOR. PER WPB UTILITIES. THE |
| | DETAIL DOES NOT COMPLY A DOUBLE SANITARY TEE WITH A CAP |
| | ON THE BOTTOM SHALL NOT BE USED. A MIN 4" TWOWAY CLEAN |
| | OUT OR PREMANUFACTERED TEST PORT SHALL BE USED PER WPB |
| | UTILITIES. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |