| 2018-01-10 12:11:32 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| | |
| | 2. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER. PER |
| | WPB AMEND TO FBC 107.2.1 THE TABLE ON THE GAS |
| | CONSUMPTION 402.4(3) IS FOR PRESSURE LESS THAN 2PSI |
| | WITH A PRESSURE DROP OF 3.0WC THE PRESSURE SHOWN ON THE |
| | PRINT IS 2PSI WITH A PRESSURE DROP OF 1PSI CLARIFY AND |
| | COMPLY WITH THE COMMENT SHOW PRESSURE ON THE RISER AND |
| | SHOW THE CORRECT TABLE |
| | |
| | 3. PLEASE INDICATE TYPE OF PIPE ON THE RISER. PER WPB |
| | AMEND TO FBC 107.2.1 THE TABLE ON THE GAS CONSUMPTION |
| | 402.4(3) IS FOR PRESSURE LESS THAN 2PSI WITH A PRESSURE |
| | DROP OF 3.0WC THE PRESSURE SHOWN ON THE PRINT IS 2PSI |
| | WITH A PRESSURE DROP OF 1PSI CLARIFY AND COMPLY WITH |
| | THE COMMENT SHOW TYPE OF PIPE ON THE RISER AND SHOW THE |
| | CORRECT TABLE |
| | |
| | 4. PLEASE PROVIDE ACCURATE SIZING TABLE THE SHOWN ON |
| | PLAN IS INCORRECT TABLE 402.4(3) IS SHOWN AS 2PSI ON |
| | THE PLAN IT IS LESS THAN 2PSI IN THE FBC FG TABLE |
| | 402.4(3) THE TABLE ON THE GAS CONSUMPTION 402.4(3) IS |
| | FOR PRESSURE LESS THAN 2PSI WITH A PRESSURE DROP OF |
| | 3.0WC THE PRESSURE SHOWN ON THE PRINT IS 2PSI WITH A |
| | PRESSURE DROP OF 1PSI CLARIFY |
| | |
| | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 PLACE |
| | NOTE ON PLAN TO PROVIDE ON JOBSITE FOR INSPECTIONS. |
| | |
| | 11. PLEASE SHOW DRIP LEGS ON RISER DIAGRAM. PER WPB |
| | AMEND TO FBC 107.2.1 THE DETAIL DOES NOT SATISFY |
| | COMMENT PLEASE SHOW ON RISER. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |