| 2017-11-21 12:11:46 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE TOILET, URINAL |
| | AND LAVATORY. PER FBC ACC 604.3.1, 605.3 AND 606.2 |
| | |
| | 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALLL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 609.4 POSITION |
| | OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE. |
| | |
| | 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| | DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. |
| | |
| | 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE |
| | WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| | LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE REAR WALL |
| | AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. |
| | |
| | 6. SHT. A2.1 DETAIL 8 AND 5 SHOWS LAVATORY RIM AT 35" |
| | OF FINISH FLOOR IT SHALL BE 34". PER FBC ACC 606.3 |
| | |
| | 7. PLEASE LIST APPLICABLE CODES. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 8. PLEASE PROVIDE A BREAK DOWN OF OCCUPANT LOAD. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. HOT WATER SYSTEM SHALL COMPLY WITH FBC PL 607.2 HOT |
| | OR TEMPERED WATER SUPPLY TO FIXTURES. |
| | THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, |
| | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT |
| | REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET |
| | . RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING |
| | SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED |
| | WATER. |
| | |
| | 10. THE WATER FILTER SHOWN ON SHT. K 2.0 DETAIL P.1 IS |
| | NOT SHOWN ON WATER PIPE RISER PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 11. A BACKFLOW IS REQUIRED ON SUPPLY TO ICE MACHINE |
| | WATER FILTER AND BEVERAGE DISPENSERS AND COFFEE |
| | MACHINES. PER FBC PL 608.3, 608.16.1 AND 608.16.10 |
| | |
| | 12. ONLY FIXTURES THAT PRODUCE GREASEY WASTE SHALL |
| | DISCHARGE THROUGH A GREASE INTERCEPTOR LIKE KITCHEN AND |
| | FOOD PREP AREA AND MOP SIN, THE FIXTURES IN BAR AREA |
| | SHALL NOT DISCHARGE THROUGH THE GREASE INTERCEPTOR. PER |
| | FBC PL 1003.2 |
| | |
| | 13. LAVATORY'S SHALL COMPLY WITH FBC PL 416.5 TEMPERED |
| | WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 14. P;LEASE SHOW ICE MACHINE ON WATER RISER. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 15. THE FIXTURE COUNT SHAL COMPLY WITH FBC PL 403.1.3 |
| | POTTY PARITY. |
| | IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO |
| | THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS |
| | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| | CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE |
| | TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH |
| | SECTION 553.86, FLORIDA STATUTES. |
| | |
| | EXCEPTION: THIS SECTION DOES NOT APPLY TO |
| | ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA |
| | STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING |
| | OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150 |
| | PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME |
| | NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL |
| | OF WATER CLOSETS AND URINALS FOR MEN. |
| | |
| | |
| | 16. A TEST PORT IS REQUIRED ON THE DISCHARGE OF GREASE |
| | INTERCEPTOR. PER WPB UTILITIES |
| | |
| | 17. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREAS |
| | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 18. WATER SYSTEM SHALL COMPLY WITH FBC PL 604.9 WATER |
| | HAMMER. |
| | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS |
| | SHALL CONFORM TO ASSE 1010. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |