| 2017-11-16 14:54:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| | 2. EXISTING RISER AND PROPOSED RISER ARE BOTH MISSING |
| | INFORMATION. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS |
| | OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| | 250.94, 408.30 |
| | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 4. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9 |
| | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. KITCHEN AND BAR AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, |
| | 405.2.2.2 |
| | 7. INSIDE THE PANEL B PANEL SCHEDULE IS A LOAD |
| | CALCULATION LABELED "PANEL A". IS THIS A TYPO? CLARIFY |
| | AND/OR CORRECT. FBC 107.2.1 |
| | 8. THERE IS A NOTE THAT STATES ALL KITCHEN AND BAR AREA |
| | RECEPTACLES SHALL BE GFCI PROTECTED, EXCEPT THOSE FOR |
| | EQUIPMENT. ALL RECEPTACLE OUTLETS ARE REQUIRED TO HAVE |
| | GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 9. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE |
| | ELECTRICAL RECEPTACLE OUTLETS LOCATED UNDER THE HOOD |
| | PER NFPA 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |