Plan Review Notes
Plan Review Notes For Permit 17101199
Permit Number 17101199
Review Stop B
Sequence Number 1
Notes
Date Text
2017-11-06 16:32:29****PLAN REVIEW COMMENTS****
  
 ART LANGE ? BUILDING PLANS EXAMINER
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 DEMOLITION PERMIT DENIED:
  
 THIS IS NOT AN INTERIOR DEMO PERMIT AS THE APPLICATION
 SHOWS. THE PLANS SHOW REMOVAL OF EXTERIOR DOORS AND
 WINDOWS. THIS CREATES A BREACH OF THE BUILDING
 ENVELOPE.
 HERE ARE A FEW OPTIONS:
  
 A) REMOVE THE EXTERIOR DOORS AND WINDOW DEMO FROM THE
 PLANS.
  
 B) SUBMIT A PERMIT FOR DOORS AND WINDOWS.
  
 C) SUBMIT AN ENGINEERED DETAIL THAT INCLUDES A METHOD
 OF SECURING THE OPENINGS AND INCLUDE A DRY IN DETAIL AS
 WELL.
  
 D) REVOKE THIS PERMIT AND INCLUDE THIS WORK AS PART OF
 YOUR BUILDING PERMIT.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOOR.)
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE. A RESPONSE LETTER INDICATING HOW
 EACH ITEM WAS ADDRESSED WILL HELP TO EXPEDITE PLAN
 REVIEW.
  