Plan Review Notes
Plan Review Notes For Permit 17101193
Permit Number 17101193
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2018-06-25 16:01:28THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) A FIRE ALARM SYSTEM IS REQUIRED AND IS INDICATED ON
 SHEET E 1. THE FIRE ALARM SYSTEM SHALL COMPLY WITH THE
 APPLICABLE CODE, INCLUDING NFPA 72.
  
 PER NFPA 101, CHAPTER 31, EXISTING APARTMENT
 OCCUPANCIES.
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
  
 PER NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE
 SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE
 OR WHERE
 SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE
 ALARM
 SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE.
 9.6.1.2 FIRE DETECTION, ALARM, AND COMMUNICATIONS
 SYSTEMS
 INSTALLED TO MAKE USE OF AN ALTERNATIVE PERMITTED BY
 THIS CODE
 SHALL BE CONSIDERED REQUIRED SYSTEMS AND SHALL MEET THE
 PROVISIONS
 OF THIS CODE APPLICABLE TO REQUIRED SYSTEMS.
 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL
 BE INSTALLED,
 TESTED, AND MAINTAINED IN ACCORDANCE WITH THE
 APPLICABLE
 REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL CODE, AND
 NFPA
 72, NATIONAL FIRE ALARM AND SIGNALING CODE, UNLESS IT
 IS AN
 APPROVED EXISTING INSTALLATION, WHICH SHALL BE
 PERMITTED TO BE
 CONTINUED IN USE.
  
 PER NFPA 72, CHAPTER 8,
  
 18.4.5 SLEEPING AREA REQUIREMENTS.
 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO
 PROVIDE
 SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND
 LEVEL OF AT
 LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5
 DB
 ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT
 LEAST
 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA,
 WHICHEVER IS
 GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA
 REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA).
 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR
 RETRACTABLE
 PARTITION, IS LOCATED BETWEEN THE NOTIFICATION
 APPLIANCE AND
 THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED
 WITH THE
 BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW.
 18.4.5.3* EFFECTIVE JANUARY 1, 2014, AUDIBLE APPLIANCES
 PROVIDED
 FOR THE SLEEPING AREAS TO AWAKEN OCCUPANTS SHALL
 PRODUCE A LOW
 FREQUENCY ALARM SIGNAL THAT COMPLIES WITH THE
 FOLLOWING:
 (1) THE ALARM SIGNAL SHALL BE A SQUARE WAVE OR PROVIDE
 EQUIVALENT
 AWAKENING ABILITY.
 (2) THE WAVE SHALL HAVE A FUNDAMENTAL FREQUENCY OF 520
 HZ
 ? 10 PERCENT.
  
  
 2) FIRE ALARM SHOP DRAWING SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT FORE APPROVAL PRIOR TO ANY WORK BEEING
 DONE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  