| 2018-03-22 15:46:24 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17101193 |
| | 3/22/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PROPOSED PROJECT SHALL BE IN COMPLIANCE WITH THE |
| | RESIDENTIAL PROVISIONS OF THE FBC-14 ENERGY |
| | CONSERVATION CODE. THE SUBMITTED FORM C402-2017 CAN NOT |
| | BE USED TO SHOW COMPLIANCE. PLEASE SEE SECTION R101.5.1 |
| | FOR ACCEPTED COMPLIANCE MATERIALS, AND SECTION R405.4.2 |
| | EXCEPTION WHICH PROVIDES COMPLIANCE INFORMATION FOR |
| | MULTIFAMILY UNITS AND MODEL HOMES. |
| | |
| | 2) THE AC COOLING AND HEATING SYSTEMS SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J. THE |
| | SUBMITTED CALCULATIONS ARE NOT IN COMPLIANCE. PLEASE |
| | NOTE THAT |
| | |
| | 3) INDICATE HOW THE APARTMENTS WILL BE VENTILATED AND |
| | PROVIDE CALCULATIONS USING EITHER NATURAL OR MECHANICAL |
| | VENTILATION- SEE SECTIONS 401.2, 402.2, AND TABLE |
| | 403.3. |
| | |
| | 4) AC CLOSETS ARE CONSIDERED PLENUM CHAMBERS PER |
| | SECTION R403.2.2, AND SHALL BE CONSTRUCTED WITH |
| | NON-COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION |
| | 602.2.1. THE WOOD LOUVERED DOOR ENCLOSING THE CLOSET |
| | CANNOT BE USED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |