Plan Review Notes
Plan Review Notes For Permit 17101193
Permit Number 17101193
Review Stop M
Sequence Number 2
Notes
Date Text
2018-03-22 15:46:242ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17101193
 3/22/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PROPOSED PROJECT SHALL BE IN COMPLIANCE WITH THE
 RESIDENTIAL PROVISIONS OF THE FBC-14 ENERGY
 CONSERVATION CODE. THE SUBMITTED FORM C402-2017 CAN NOT
 BE USED TO SHOW COMPLIANCE. PLEASE SEE SECTION R101.5.1
 FOR ACCEPTED COMPLIANCE MATERIALS, AND SECTION R405.4.2
 EXCEPTION WHICH PROVIDES COMPLIANCE INFORMATION FOR
 MULTIFAMILY UNITS AND MODEL HOMES.
  
 2) THE AC COOLING AND HEATING SYSTEMS SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J. THE
 SUBMITTED CALCULATIONS ARE NOT IN COMPLIANCE. PLEASE
 NOTE THAT
  
 3) INDICATE HOW THE APARTMENTS WILL BE VENTILATED AND
 PROVIDE CALCULATIONS USING EITHER NATURAL OR MECHANICAL
 VENTILATION- SEE SECTIONS 401.2, 402.2, AND TABLE
 403.3.
  
 4) AC CLOSETS ARE CONSIDERED PLENUM CHAMBERS PER
 SECTION R403.2.2, AND SHALL BE CONSTRUCTED WITH
 NON-COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 602.2.1. THE WOOD LOUVERED DOOR ENCLOSING THE CLOSET
 CANNOT BE USED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  