2018-03-16 12:25:342014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17101193
 ADD: 325 S. LAKESIDE CT. / 3 FLOORS OF RENOVATION
 CONT: BEACON CONSTRUCTION GROUP
 TEL: 561-845-5130
 E-MAIL: ROGER@BEACONCONSTRUCTION GROUP.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: FRI. MARCH 16/ 2018
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SEMI-COMPLIED. WITH THE EXCEPTION OF THE STUDIO
 APARTMENT ALL OF THE OTHER NEW SHOWER COMPARTMENTS ARE
 IN THE TENANT SEPARATION WALL WITH ANOTHER R-2 UNIT ON
 THE OTHER SIDE OF THE WALL. PLEASE SHOW HOW COMPLIANCE
 WITH:
  
 2014 FBC-B SECTION 420.2 IS ACHIEVED AS WELL AS 2509.2.
 FOR SECTION 2509.2 SEE 1ST ROUND OF COMMENTS.
  
 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING UNITS
 IN THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND WALLS SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE
 PARTITIONS IN ACCORDANCE WITH SECTION 708.
  
 FBC-B SECTION 708.3 FIRE-RESISTANCE RATING. FIRE
 PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR.
  
 THE PRESCRIPTIVE METHOD FOR FIRE RESISTANCE SHOULD
 QUOTE THE SECTION FOR EXAMPLE INTERIOR WALL PER
 721.1(2) 14-1.2. THIS WOULD BE GOOD FOR THE ? DRYWALL
 BUT ALSO PROVIDE A WALL DETAIL FOR THE CEMENT BACKER
 BOARD AS WELL. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1ST ROUND OF COMMENTS. SHEET A-1 UNDER THE SCOPE OF
 WORK, COMMENT # 9 INDICATES THE REMOVAL AND REPLACEMENT
 OF TUB. THE PLANS DOES NOT INDICATE THE TUB SURROUND TO
 BE REWORKED BUT THE REMOVAL OF THE TUB, THEY USUALLY
 NEED REPLACEMENT. IF SO THEY WILL NEED TO COMPLY WITH
 2014 FBC-B SECTION;
 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR
 C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS.
  
 4) 2ND REQUEST. PLEASE NOTE THE PLANS INDICATE THE
 INSTALLATION OF SUPER SAM 125. PLEASE SUPPLY THE ACTUAL
 TEST REPORTS WHERE SUPER SAM 125 HAS BEEN TESTED ON
 WOOD FLOOR JOIST AND WITH THE CONFIGURATION OF ONE ?
 INCH TONGUE AND GROOVE PLYWOOD DECKING. THE PLANS ALSO
 ONLY SHOW ONLY 1 LAYER OF ? INCH DRYWALL ON THE
 CEILING. WE WILL NEED TO SEE TEST REPORTS FOR BOTH THE
 STRUCTURE-BORNE SOUND TESTED IN ACCORDANCE WITH ASTM E
 492 AND AIR-BORNE SOUND TESTED IN ACCORDANCE WITH ASTM
 E 90.
 THE SUPER SAM 125 FLAME SPREAD TEST IS ACCEPTABLE.
  
 1ST ROUND OF COMMENTS. SHEET A-1 UNDER THE SCOPE OF
 WORK, COMMENT # 7 INDICATES THE INSTALLATION OF TILE
 OVER EXISTING WOOD FLOORING. NOTE FOR THE 2ND AND 3RD
 FLOOR UNITS WILL NEED TO PROVIDE SOUND UNDERLAYMENT
 BEFORE THE TILE IS INSTALLED. FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS. PLEASE PROVIDE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) SHEET A-2. NEW COMMENT HAS TO DEAL WITH THE FLOOR/
 CEILING ASSEMBLY ON THE 2ND AND 3RD FLOORS. THE PLAN
 DOES NOT CALL OUT ANY UL ASSEMBLY OR GYPSUM FLOOR
 CEILING ASSEMBLY. USING THE 2014 FBC-B UNDER THE
 PRESCRIPTIVE FIRE RESISTANCE METHOD AND TABLE
 721.1(3)13-1.4 WITH A DOUBLE WOOD FLOOR SYSTEM, JOIST
 AT 16 INCHES ON CENTER WITH ? INCH TYPE X DRYWALL.
  
 2014 FBC-B SECTION 420 GROUP R-1, R-2, R-3 & I-1.
 ? 420.3 HORIZONTAL SEPARATION.
 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH
 SECTION 711.
  
 FBC-B 711.3 FIRE-RESISTANCE RATING. HORIZONTAL
 ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDING AND HORIZONTAL ASSEMBLIES SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING SHALL BE A MINIMUM OF 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION. EXCEPTION: DWELLING
 UNIT AND SLEEPING UNIT SEPARATIONS IN BUILDINGS OF TYPE
 IIB, IIIB AND VB CONSTRUCTION SHALL HAVE
 FIRE-RESISTANCE RATINGS OF NOT LESS THAN 1/2 HOUR IN
 BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1.
  
 6) SHEET A-2. NEW COMMENT. SEE DETAIL #2 INDICATES A
 DROPPED SOFFIT BUT THERE IS NO FIRE RATING AT THE FLOOR
 / CEILING ASSEMBLY. 718.2 FIREBLOCKING. IN COMBUSTIBLE
 CONSTRUCTION, FIREBLOCKING SHALL BE INSTALLED TO CUT
 OFF CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND
 HORIZONTAL) AND SHALL FORM AN EFFECTIVE BARRIER BETWEEN
 FLOORS.
  
 7) 2014 EXISTING BUILDING CODE 804.4.1.6 GROUP R-2. A
 FIRE ALARM SYSTEM SHALL BE INSTALLED IN WORK AREAS OF
 GROUP R-2 APARTMENT BUILDINGS AS REQUIRED BY THE
 FLORIDA FIRE PREVENTION CODE FOR EXISTING GROUP R-2
 OCCUPANCIES.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER