| 2017-12-05 15:02:02 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. IT APPEARS THAT 2 DIFFERENT METHODS WERE |
| | COMBINED TO PROVIDE CALCULATION, WHICH IS NOT TO |
| | COMPLIANT WITH CODE. ALSO, WILL THERE BE A HOUSE PANEL |
| | ON THIS SERVICE? THIS LOAD SHOULD BE INCLUDED. BASED ON |
| | CURRENT CONFIGURATION, IT APPEARS THAT ONE OF THE 400 |
| | AMP MAINS WILL BE OVERLOADED. PROVIDE CORRECTION AS |
| | NEEDED. NEC 215.2, 220; FBC 107.2.1 |
| | 2. FEEDERS FROM METER CENTER TO INDIVIDUAL UNIT PANELS |
| | REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE |
| | CORRECTION. NEC 250.122 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94 |
| | 4. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH |
| | IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT |
| | 125% OF THE LOAD, WHICH WOULD BE A 25 AMP BREAKER. |
| | PROVIDE CORRECTION. NEC 422.13; FBC RE3702.10 |
| | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 6. PROVIDE NOTE FOR AFCI PROTECTION PER NEC 210.12: |
| | "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION." NEC 210.12 |
| | 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |