| 2017-11-08 11:44:57 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE MOUNTING DIMENSIONS FOR ACCESSIBILITY |
| | IN THE BATHROOMS SHALL COMPLY WITH FBC ACC 609.4 |
| | POSITION OF GRAB BARS. 604.5.2 REAR WALL. 604.5.1 SIDE |
| | WALL. / 604.7 DISPENSERS. / 603.3 MIRRORS. / LAVATORY |
| | 606.3 HEIGHT. |
| | |
| | 2. PROVIDE MANUFACTURE SIZING CALCULATION FOR THE |
| | SCHIER GB 250 GREASE INTERCEPTOR. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 3. PROVIDE TEST PORT ON OUTLET OF GREASE INTERCEPTOR . |
| | PER WPB AMEND TO FBC 107.2.1 WPB UTILITIES DEPT. |
| | |
| | 4. THE DRAIN FOR THE FUTURE BAR AREA AND THE HUB DRAIN |
| | FOR THE ICE MACHINE SHALL NOT CONNECT TO THE GREASY |
| | WASTE SYSTEM. DISCHARGE FROM FIXTURES OR APPLIANCES |
| | THAT DO NOT PRODUCE GREASE WASTE SUCH AS SINKS IN BAR |
| | AREAS WITH NO FOOD PREP OR COOKING OR ICE MACHINES AND |
| | BINS SHALL NOT DISCHARGE INTO GREASE INTERCEPTORS. PER |
| | FBC PL 1003.2 AND 1003.3.1 |
| | |
| | 5. WHAT IS THE 3" HUB DRAIN ON THE GREASE RISER |
| | DRAINING IF IT IS THE ICE MACHINE IT SHALL NOT CONNECT |
| | TO THE GREASE LINE. PER FBC PL 1003.2 AND 1003.3.1 |
| | |
| | 6. WHAT IS THE AAV PIPE DRAINING INTO THE MOST UPSTREAM |
| | FLOOR SINK ON THE GREASE RISER PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 7. A MIN OF 1 OF THE VENTS ON THE GREASY WASTE SYSTEM |
| | SHALL TERMINATE OUTDOORS. PER FBC PL 904.1 |
| | |
| | 8. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW |
| | PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. THE LAVATORY'S SHALL COMPLY WITH FBC PL 416.5 |
| | TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |