Plan Review Notes
Plan Review Notes For Permit 17101173
Permit Number 17101173
Review Stop P
Sequence Number 1
Notes
Date Text
2017-11-08 11:44:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE MOUNTING DIMENSIONS FOR ACCESSIBILITY
 IN THE BATHROOMS SHALL COMPLY WITH FBC ACC 609.4
 POSITION OF GRAB BARS. 604.5.2 REAR WALL. 604.5.1 SIDE
 WALL. / 604.7 DISPENSERS. / 603.3 MIRRORS. / LAVATORY
 606.3 HEIGHT.
  
 2. PROVIDE MANUFACTURE SIZING CALCULATION FOR THE
 SCHIER GB 250 GREASE INTERCEPTOR. PER WPB AMEND TO FBC
 107.2.1
  
 3. PROVIDE TEST PORT ON OUTLET OF GREASE INTERCEPTOR .
 PER WPB AMEND TO FBC 107.2.1 WPB UTILITIES DEPT.
  
 4. THE DRAIN FOR THE FUTURE BAR AREA AND THE HUB DRAIN
 FOR THE ICE MACHINE SHALL NOT CONNECT TO THE GREASY
 WASTE SYSTEM. DISCHARGE FROM FIXTURES OR APPLIANCES
 THAT DO NOT PRODUCE GREASE WASTE SUCH AS SINKS IN BAR
 AREAS WITH NO FOOD PREP OR COOKING OR ICE MACHINES AND
 BINS SHALL NOT DISCHARGE INTO GREASE INTERCEPTORS. PER
 FBC PL 1003.2 AND 1003.3.1
  
 5. WHAT IS THE 3" HUB DRAIN ON THE GREASE RISER
 DRAINING IF IT IS THE ICE MACHINE IT SHALL NOT CONNECT
 TO THE GREASE LINE. PER FBC PL 1003.2 AND 1003.3.1
  
 6. WHAT IS THE AAV PIPE DRAINING INTO THE MOST UPSTREAM
 FLOOR SINK ON THE GREASE RISER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 7. A MIN OF 1 OF THE VENTS ON THE GREASY WASTE SYSTEM
 SHALL TERMINATE OUTDOORS. PER FBC PL 904.1
  
 8. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 9. THE LAVATORY'S SHALL COMPLY WITH FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  