Plan Review Notes
Plan Review Notes For Permit 17101173
Permit Number 17101173
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-02 17:54:411ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17101173
 11/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SMOKE DETECTOR IN THE RETURN AIR SYSTEM OF
 THE 5-TON AC SYSTEM PER SECTION 606.2.1. PLEASE NOTE
 THAT AN EXEMPTION CAN BE APPLIED IF THE MANUFACTURER'S
 SPECIFICATIONS INDICATE THE SYSTEMS IS NOT CAPABLE OF
 PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 2) PROVIDE AN AUTOMATICALLY CONTROLLED SHUT OFF DAMPER
 FOR THE O/A INTAKE DUCT- EITHER MOTORIZED OT GRAVITY IS
 ACCEPTABLE PER SECTION C403.2.4.4. FBC-14 ENERGY
 CONSERVATION.
  
 3) THE O/A CALCULATIONS INDICATE A HIGH PERCENTAGE OF
 AIR- APPROXIMATELY 30%- TO BE CONDITIONED BY THE 5-TON
 SYSTEM. PER MANUFACTURER'S RECOMMENDATIONS, IS THIS
 EXISTING SYSTEM LARGE ENOUGH TO HANDLE THE INCREASED
 AMOUNT OF OUTSIDE AIR?
  
 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED APPLIANCES IN THE KITCHEN, AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SEE SECTION 304 FBC-14 FUEL
 GAS.
  
 5) SUBMIT CUT SHEETS FOR THE GAS-FIRED COOKING
 APPLIANCES- SECTION
  
 6) ADVISORY NOTES FOR THE EXTERIOR WALK-IN COOLER:
 PLEASE SEE THE BUILDING REVIEW COMMENTS REGARDING THE
 FLOOD ELEVATION HEIGHT REQUIREMENT FOR THE PROPOSED
 FOUNDATION, AND SECTION 301.16 FBC-14 MECHANICAL.
 ADDITIONALLY, PLEASE NOTE THAT EXTERIOR WALK IN COOLERS
 MUST HAVE FLORIDA PRODUCT APPROVAL OR BE APPROVED AS A
 MANUFACTURED BUILDING.
  
 7) ADVISORY FOR THE KITCHEN HOOD: SECTION 508.1.1
 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  