2017-11-08 12:14:541ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. PREVIOUS GAS PERMIT SHOWS A NATURAL GAS SYSTEM THERE
 IS NO RECORDS OF EXISTING LP GAS TANK PLEASE CLARIFY.
 WPB AMEND TO FBC 107.2.1
  
 2. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 3. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF THE
 TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 4. PLEASE SHOW THE DISTANCE, SIZE AND PRESSURE OF THE
 PIPE FROM THE LP TANK TO FIRST REG. PER FBC FUEL GAS
 CODE SEC. 402.4.1. AND WPB AMEND TO FBC 107.2.1
  
 5. THE GAS RISER DOES NOT MATCH THE FLOOR PLAN THE
 RISER SHOWS THE SERVICE COMING IN NEXT TO TANKLESS
 HEATER THE FLOOR PLAN SHOWS SERVICE COMING IN ON
 OPPOSITE SIDE OF BUILDING PLEASE CLARIFY. WPB AMEND TO
 FBC 107.2.1
  
 6. WHAT APPLIANCE IS SHOWN AT THE END OF THE RISER ON A
 1" LINE LABEL BTU LOAD. WPB AMEND TO FBC 107.2.1
  
 7. SIZE THE BRANCH FEEDING TANKLESS WATER HEATER. WPB
 AMEND TO FBC 107.2.1
  
 8. THE GAS LOAD CALCULATIONS LIST 8 APPLIANCES THE
 RISER SHOWS 7 THE FLOOR PLAN SHOWS 7 IN DIFFERENT
 LOCATIONS THE KITCHEN EQUIPMENT SCHEDULE SHOWS 5 PLUS
 TANKLESS HEATER PLEASE CLARIFY. WPB AMEND TO FBC
 107.2.1
  
 9. THE GAS LOAD CALCULATIONS LIST THE 2004 FBC FUEL GAS
 CODE THE CURRENT CODE SHALL BE 2014 FBC FG 5TH EDITION.
 WPB AMEND TO FBC 107.2.1
  
 10. PLEASE LIST SIZING TABLES FROM FBC FG USED IN
 SIZING SYSTEM. WPB AMEND TO FBC 107.2.1
  
 11. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 12. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 13. THE TANKLESS WATER HEATER SHALL BE MOUNTED A MIN OF
 4' FROM ANY OPERABLE WINDOWS OR DOORS. PER MANUFACTURE
 INSTILLATION GUIDE
  
 14. BTU LOAD FOR WATER HEATER SHOWN ON RISER AS 180,000
 AND 199,000 ON WATER HEATER DETAIL CLARIFY. WPB AMEND
 TO FBC 107.2.1
  
 15. WATER HEATER DETAIL LIST RINNAI THE FLOOR PLAN LIST
 A NORITZ TANKLESS HEATER PLEASE CLARIFY. WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  