| 2017-11-08 12:14:54 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. PREVIOUS GAS PERMIT SHOWS A NATURAL GAS SYSTEM THERE |
| | IS NO RECORDS OF EXISTING LP GAS TANK PLEASE CLARIFY. |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| | PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 3. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE |
| | OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF THE |
| | TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS |
| | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED |
| | PER NFPA 58 SECTION 3-2.2.7(H). |
| | |
| | 4. PLEASE SHOW THE DISTANCE, SIZE AND PRESSURE OF THE |
| | PIPE FROM THE LP TANK TO FIRST REG. PER FBC FUEL GAS |
| | CODE SEC. 402.4.1. AND WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. THE GAS RISER DOES NOT MATCH THE FLOOR PLAN THE |
| | RISER SHOWS THE SERVICE COMING IN NEXT TO TANKLESS |
| | HEATER THE FLOOR PLAN SHOWS SERVICE COMING IN ON |
| | OPPOSITE SIDE OF BUILDING PLEASE CLARIFY. WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 6. WHAT APPLIANCE IS SHOWN AT THE END OF THE RISER ON A |
| | 1" LINE LABEL BTU LOAD. WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SIZE THE BRANCH FEEDING TANKLESS WATER HEATER. WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 8. THE GAS LOAD CALCULATIONS LIST 8 APPLIANCES THE |
| | RISER SHOWS 7 THE FLOOR PLAN SHOWS 7 IN DIFFERENT |
| | LOCATIONS THE KITCHEN EQUIPMENT SCHEDULE SHOWS 5 PLUS |
| | TANKLESS HEATER PLEASE CLARIFY. WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 9. THE GAS LOAD CALCULATIONS LIST THE 2004 FBC FUEL GAS |
| | CODE THE CURRENT CODE SHALL BE 2014 FBC FG 5TH EDITION. |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. PLEASE LIST SIZING TABLES FROM FBC FG USED IN |
| | SIZING SYSTEM. WPB AMEND TO FBC 107.2.1 |
| | |
| | 11. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2014 FUEL GAS CODE SEC. 304. |
| | |
| | 12. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| | |
| | 13. THE TANKLESS WATER HEATER SHALL BE MOUNTED A MIN OF |
| | 4' FROM ANY OPERABLE WINDOWS OR DOORS. PER MANUFACTURE |
| | INSTILLATION GUIDE |
| | |
| | 14. BTU LOAD FOR WATER HEATER SHOWN ON RISER AS 180,000 |
| | AND 199,000 ON WATER HEATER DETAIL CLARIFY. WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 15. WATER HEATER DETAIL LIST RINNAI THE FLOOR PLAN LIST |
| | A NORITZ TANKLESS HEATER PLEASE CLARIFY. WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |