2017-11-06 16:15:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE APPEARS TO BE SOME QUESTIONS FROM THE BUILDING
 DEPT. THAT NEED TO BE ADDRESSED. ANY APPROVAL BY FIRE
 WILL NEED TO HAVE THESE CONCERNS CORRECTED.
  
  
  
 2) SHEET 1.2A - THERE IS AN EXIT SIGN ON THE REAR WALL
 BY THE KITCHEN. THIS SIGN NEEDS TO BE REMOVED.
  
 PLEASE REMOVE SIGN.
  
  
  
 3) SHEET 1.2A - THERE IS AN INDICATION THAT THE
 OCCUPANCY LOAD IN THE DINING AREA OF 411 SQ/FT IS 27.
  
 411 SQ/FT / 15 = 27.4 = 28 PEOPLE.( ROUND UP)
  
 PLEASE CORRECT TO 28 AND TOTAL APPLICABLE OCCUPANY
 COUNT.
  
  
 4) SHEET 1.2A - THE SEATING PLAN SUBMITTED INDICATES 35
 SEATS IN THE DINING AREA. THIS AREA IS LIMITED TO 28
 PER # 3 ABOVE.
  
 PLEASE CORRECT SEAT COUNT TO 28.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL