| 2017-11-09 07:53:26 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| | 2. PROVIDE COMPLETE RISER DIAGRAM, SHOWING ALL DETAILS |
| | OF SERVICE EQUIPMENT, INCLUDE WIRE AND BREAKER SIZES |
| | FOR SERVICE AND FEED TO INTERIOR PANEL. SHOW GEC SIZE |
| | AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT. |
| | NEC 215.5, 230, 250.50, 250.94, 408.30 |
| | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 4. NOTE 22 STATES THERE IS A LIGHTING CONTROL SYSTEM TO |
| | BE INSTALLED, BUT IT IS NOT SHOWN ON PLAN. PROVIDE |
| | LOCATION ON PLAN AND SPEC SHEET FOR SYSTEM. NEC 110.3; |
| | FBC 107.2.1 |
| | 5. NOTE 19 STATES THERE WILL BE OCCUPANCY SENSORS FOR |
| | LIGHTING IN LARGER AREAS, BUT THIS IS NOT SHOWN ON |
| | PLAN. PROVIDE LOCATION ON PLAN AND SPEC SHEET FOR |
| | OCCUPANCY SENSORS. NEC 110.3; FBC 107.2.1 |
| | 6. THERE IS A SWITCH SYMBOL THAT IS NOT ON THE LEGEND. |
| | IT APPEARS TO RESEMBLE A SINGLE POLE SWITCH, BUT IT HAS |
| | AN "O" INSTEAD OF AN "S" . CLARIFY AND ADD TO LEGEND. |
| | FBC 107.2.1 |
| | 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE. NEC 110.9, 110.10 |
| | 8. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. |
| | NEC 110.3, 110.9 |
| | 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. NEC 210.63 |
| | 10. PROVIDE DETAILS OF WIRING TO MECHANICAL EQUIPMENT |
| | ON POWER PLAN. CURRENTLY, NONE OF THE MECHANICAL |
| | EQUIPMENT IS SHOWN ON POWER PLAN. FBC 107.2.1 |
| | 11. IN THE OFFICE, THERE IS A SYMBOL THAT IS A CIRCLE |
| | WITH A "D" INSIDE. WHAT IS THIS FOR? CLARIFY AND ADD |
| | SYMBOL TO LEGEND. FBC 107.2.1 |
| | 12. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC |
| | 600.5; FBC CE 405.2.4 |
| | 13. PROVIDE CIRCUIT AND OUTLETS FOR SHOW WINDOW |
| | RECEPTACLES. NEC 210.62 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |