Plan Review Notes
Plan Review Notes For Permit 17101173
Permit Number 17101173
Review Stop E
Sequence Number 1
Notes
Date Text
2017-11-09 07:53:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
 2. PROVIDE COMPLETE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, INCLUDE WIRE AND BREAKER SIZES
 FOR SERVICE AND FEED TO INTERIOR PANEL. SHOW GEC SIZE
 AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT.
 NEC 215.5, 230, 250.50, 250.94, 408.30
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 4. NOTE 22 STATES THERE IS A LIGHTING CONTROL SYSTEM TO
 BE INSTALLED, BUT IT IS NOT SHOWN ON PLAN. PROVIDE
 LOCATION ON PLAN AND SPEC SHEET FOR SYSTEM. NEC 110.3;
 FBC 107.2.1
 5. NOTE 19 STATES THERE WILL BE OCCUPANCY SENSORS FOR
 LIGHTING IN LARGER AREAS, BUT THIS IS NOT SHOWN ON
 PLAN. PROVIDE LOCATION ON PLAN AND SPEC SHEET FOR
 OCCUPANCY SENSORS. NEC 110.3; FBC 107.2.1
 6. THERE IS A SWITCH SYMBOL THAT IS NOT ON THE LEGEND.
 IT APPEARS TO RESEMBLE A SINGLE POLE SWITCH, BUT IT HAS
 AN "O" INSTEAD OF AN "S" . CLARIFY AND ADD TO LEGEND.
 FBC 107.2.1
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE. NEC 110.9, 110.10
 8. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63
 10. PROVIDE DETAILS OF WIRING TO MECHANICAL EQUIPMENT
 ON POWER PLAN. CURRENTLY, NONE OF THE MECHANICAL
 EQUIPMENT IS SHOWN ON POWER PLAN. FBC 107.2.1
 11. IN THE OFFICE, THERE IS A SYMBOL THAT IS A CIRCLE
 WITH A "D" INSIDE. WHAT IS THIS FOR? CLARIFY AND ADD
 SYMBOL TO LEGEND. FBC 107.2.1
 12. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC CE 405.2.4
 13. PROVIDE CIRCUIT AND OUTLETS FOR SHOW WINDOW
 RECEPTACLES. NEC 210.62
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746