2017-11-02 10:41:432014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17101173
 ADD: 1156 ELIZABETH AVE.
 CONT: KEMKON PROPERTIES INC.
 TEL: 561-512-7637
 E-MAIL: [email protected]
 [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 02/ 2017
 ACTION: DENIED
  
 1) CREATION OR EXTENSION OF NONCONFORMITY. PLEASE NOTE
 THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE DOES
 NOT SHOW THE SAME SQUARE FOOTAGE FOR THIS BUILDING AS
 THE SUBMITTED DEPICTED PLANS. THE FOOT PRINT OF THE
 BUILDING RECORDED WITH THE PROPERTY APPRAISERS OFFICE
 WOULD BE THE SAME IF THE KITCHEN WAS NOT THERE. IN
 REVIEWING P. B. COUNTY AERIAL PHOTOGRAPHY IN 2006
 EXTERIOR WALLS OF AN ADDITION WERE ERECTED. THEN IN
 2009 THE P. B. COUNTY AERIAL PHOTOGRAPHS SHOW A
 FINISHED ROOF. I HAVE REVIEWED THE PERMIT RECORDS FOR
 BOTH ADDRESSES 1156 ELIZABETH AVE. AND 1177 CLARE AVE
 AND FOUND NO RECORDS FOR AN ADDITION AT THIS ADDRESS.
 IN REVIEWING THE CITY PERMIT RECORDS UNDER PERMIT
 06082252 FOR 1177 CLARE AVE. THERE WAS A SURVEY THAT
 DIDN?T SHOW ANY ADDITION OR CURRENT KITCHEN. THE SURVEY
 SHOWED THE SAME FOOTPRINT AS THE PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE. THE ILLEGAL ADDITION WILL
 BE TREATED AS NEW WORK AND NEED TO MEET THE REGULATIONS
 OF THE 2014 FBC-B.
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 SINCE THE ADDITION WAS NOT PERMITTED IT IS CONSIDERED
 NEW WORK. 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2) PLEASE INCREASE THE VALUE OF THE PERMIT TO INCLUDE
 THE UNPERMITTED WORK IS NOT REFLECTED IN THE PERMIT
 VALUE THE INCREASE IN SQUARE FOOT AREA OF 16 X 41 = 656
 SQ. FEET @ A VALUE OF 105.82 A SQUARE FOOT. NOTE THIS
 VALUE IS TAKEN FROM THE AUGUST 2006 IBC EVALUATION
 TABLES FOR RESTAURANT TYPE VB CONSTRUCTION OR A DOLLAR
 AMOUNT OF $59,894.12 DOLLARS. 4 TIMES THE PERMIT FEE
 WOULD BE ASSESSED AGAINST THIS PERMIT.
  
 3) PLEASE NOTE THIS BUILDING (ADDRESSES 1156 ELIZABETH
 AVE) IS IN A FLOOD ZONE. THERE IS IN THE P. B. COUNTY
 PROPERTY APPRAISERS OFFICE FOR THIS ADDRESS 3 BUILDINGS
 IMPROVEMENT VALUE, NO LAND, OF $770,273.00/ 17217 SQ.
 FT. = $44.74 DOLLARS PER SQ. FT. BUILDING # 2 TOTAL SQ.
 FT. 1300 X $44.74.00 = $58,162.00 DOLLARS OF
 IMPROVEMENT VALUE FOR BUILDING # 2.
  
 BUILDING # 2 IMPROVEMENT VALUE $58,162.00
  
 ILLEGAL ADDITION VALUE OF: $59,894.00
 PERMIT RENOVATION VALUE OF: $75,000.00
 TOTAL VALUE: $134,894.00 SUBSTANTIAL IMPROVEMENT
  
 PLEASE NOTE THE ORIGINAL BUILDING WAS BUILT IN 1935
 PRE-FIRM. IF NO WORK COULD OCCURRED MAKING THE BUILDING
 MEET THE SUBSTANTIAL IMPROVEMENT.
 THE ILLEGAL ADDITION IS VALUE IS WORTH MORE THAN THE
 VALUE OF THE BUILDING # 2. WITH THE PROPOSED PERMIT
 VALUE AND ILLEGAL ADDITION THE SUBSTANTIAL IMPROVEMENT
 VALUE IS 4 TIMES THE VALUE TO MEET SUBSTANTIAL
 IMPROVEMENT.
  
 SUBSTANTIAL IMPROVEMENT DESK REFERENCE, PAGE 6-9, TABLE
 6-1A.
 TYPE OF WORK, LATERAL ADDITION, SUBSTANTIAL ADDITION,
 STRUCTURALLY CONNECTED, BOTH THE ADDITION AND BUILDING
 WILL NEED TO COMPLY.
  
 SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR
 FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR,
 RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE
 CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT
 OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF
 NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE.
  
 PLEASE NOTE PERMITS APPLIED FOR AFTER OCT. 11/2017 WILL
 NEED TO HAVE A FINISH FLOOR 2 FEET ABOVE THE BASE
 FLOOD. ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD
 PREVENTION & CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF
 PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 PLEASE ALSO NOTE THAT ON THE DATE OCT. 12TH/ 2017 THE
 CITY ADOPTED THE NEW FLOOD ORDINANCE, THE NEW FLOOD
 MAPS WENT INTO AFFECT WITH THE NAV88 NOMENCLATURE AND 2
 FOOT FREEBOARD REQUIREMENT.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. W.
 P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) PLEASE NOTE IN AUGUST 2016 THE ASSISTANT BUILDING
 OFFICIAL MR. STEVEN KENNEDY REQUEST FOR DETERMINATION
 TO RESOLVE THE OUTSTANDING/ EXPIRED PERMITS FOR THIS
 SITE ADDRESS, 1156 ELIZABETH AVE. AND 1177 CLARE.
 PLEASE NOTE IF ACTION IS NOT TAKEN IMMEDIATELY TO
 RESOLVE THE UNPERMITTED WORK AND EXPIRED PERMITS WE
 WILL TURN THIS MATTER OVER TO CODE ENFORCEMENT AND THEN
 TO THE SPECIAL MASTER FOR A HEARING.
  
 4) PLEASE EITHER PROVIDE A EXISTING FLOOR PLAN OR A
 INTERIOR DEMO PLAN TO VIEW WHAT IS EXISTING AND WHAT IS
 PROPOSED NEW WORK, THIS MAY TIE IN WITH EXPIRED
 PERMITS? 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 5) PLEASE SEE THE 2014 FLORIDA ENERGY CODE,
 DEFINITIONS: RENOVATED BUILDING. A RESIDENTIAL OR
 NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT
 VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
 THIS BUILDING WILL NEED TO SHOW COMPLIANCE, 2014 ENERGY
 CODE C101.5. COMMERCIAL BUILDINGS SHALL MEET THE
 COMMERCIAL PROVISIONS.
 C401.1 SCOPE.
 THE REQUIREMENTS CONTAINED IN THIS CHAPTER ARE
 APPLICABLE TO COMMERCIAL BUILDINGS, OR PORTIONS OF
 COMMERCIAL BUILDINGS.
  
 C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
 C401.2.1 APPLICATION TO EXISTING BUILDINGS.
 ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. SECTIONS C402, C403, C404 AND C405; OR
 2. ANSI/ASHRAE/IESNA 90.1.
  
 6) PLEASE PROVIDE CHANGE IN GRADE THROUGH THE FLOOR
 PLAN TO SHOW COMPLIANCE WITH: 2014 ACCESS. CODE 206.4.1
 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES REQUIRED BY
 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL
 PUBLIC ENTRANCES SHALL COMPLY WITH 404. SHEET 1.0A
 SHOWS A NEW DOORWAY LEADING TO THE EXTERIOR OF THE
 BUILDING, THE PLAN DOES NOT DECLARE THE USAGE OF THE
 INTERIOR AREA JUST INSIDE OF THE DOORWAY, IS THIS AREA
 OPEN TO THE PUBLIC AS AN EXIT?
  
 7) THE LIFE SAFETY SHEET 1.0A DOES NOT SHOW COMPLIANCE
 WITH THE 2014 FBC-ACCESSIBILITY CODE;
 7A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 7B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 7C) DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO,
 BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF
 WORK SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 7D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 7D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8) SHEET A.0A) SHOWS THE EXISTING RESTROOMS, PLEASE
 NOTE WE HAVE NO PERMITS PULLED FOR EITHER ADDRESS 1156
 ELIZABETH OR 1177 CLARE SHOWING ACCESSIBLE TOILET
 UPGRADES.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (10.) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 9) THE PLANS ARE LACKING DETAILS FOR NEW WINDOW AND
 DOOR OPENINGS:
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 FOUNDATION
 FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612,
 INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
  
 10) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 12) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 13) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  