Plan Review Notes
Plan Review Notes For Permit 17101162
Permit Number 17101162
Review Stop B
Sequence Number 3
Notes
Date Text
2018-03-23 16:20:07****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 THIRD REVIEW:
  
 REPEATED COMMENT FROM LAST REVIEW AND ADDITIONAL
 COMMENTS REGARDING THE COLLATING THE PLANS.
  
 A. TWO COMPLETE SETS OF PLANS NOT PROVIDED.
  
 B. PAGES NOT IN INDEX. AD 1.1, E 2.2, P 1.1
  
 C. BOTH SETS HAVE DUPLICATED ELECTRICAL PAGES.
  
 D. BOTH SETS HAVE DUPLICATED MECHANICAL PAGES.
  
 E. ONE SET MISSING A 6.1, A 8.1, A 9.0 AND A 9.1
  
 F. PAGE E 3.1 NOT PROVED BOTH SETS.
  
 G. PUT TOGETHER TWO COMPLETE SETS OF PLANS FOR REVIEW.
 ADD THE MISSING PAGES TO THE INDEX. ORGANIZE THE PAGES
 IN THE ORDER OF THE INDEX.
  
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHERE APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 4X FEES PLAN REVIEW FEE
  
 F.S. 553.80 (2) (B)
  
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 PREVIOUS COMMENTS:
  
 COMPLETE SETS OF PLANS NOT PROVIDED.
 ONLY ONE SET OF THE FOLLOWING PAGES FOUND.
 IC1.0, IC1.1, LS 1.1, A1.1, A6.1, A8.1, A9.0 AND A9.1
  
 SUBMIT A MINIMUM OF TWO SETS OF PLANS FOR REVIEW. FBC
 107.1
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.