| 2018-03-23 16:20:07 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE - BUILDING INSPECTOR |
| | 561-805-6667 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION |
| | |
| | THIRD REVIEW: |
| | |
| | REPEATED COMMENT FROM LAST REVIEW AND ADDITIONAL |
| | COMMENTS REGARDING THE COLLATING THE PLANS. |
| | |
| | A. TWO COMPLETE SETS OF PLANS NOT PROVIDED. |
| | |
| | B. PAGES NOT IN INDEX. AD 1.1, E 2.2, P 1.1 |
| | |
| | C. BOTH SETS HAVE DUPLICATED ELECTRICAL PAGES. |
| | |
| | D. BOTH SETS HAVE DUPLICATED MECHANICAL PAGES. |
| | |
| | E. ONE SET MISSING A 6.1, A 8.1, A 9.0 AND A 9.1 |
| | |
| | F. PAGE E 3.1 NOT PROVED BOTH SETS. |
| | |
| | G. PUT TOGETHER TWO COMPLETE SETS OF PLANS FOR REVIEW. |
| | ADD THE MISSING PAGES TO THE INDEX. ORGANIZE THE PAGES |
| | IN THE ORDER OF THE INDEX. |
| | |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHERE APPROVED BY THE |
| | BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | |
| | 4X FEES PLAN REVIEW FEE |
| | |
| | F.S. 553.80 (2) (B) |
| | |
| | (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | PREVIOUS COMMENTS: |
| | |
| | COMPLETE SETS OF PLANS NOT PROVIDED. |
| | ONLY ONE SET OF THE FOLLOWING PAGES FOUND. |
| | IC1.0, IC1.1, LS 1.1, A1.1, A6.1, A8.1, A9.0 AND A9.1 |
| | |
| | SUBMIT A MINIMUM OF TWO SETS OF PLANS FOR REVIEW. FBC |
| | 107.1 |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |