| 2017-11-18 12:17:41 | 1ST REVIEW FBC-2014 MECHANICAL CODE, GUIDELINES FOR |
| | DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES-2010 |
| | PERMIT #17101162 |
| | 11/18/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M3.1: PROVIDE THE CURRENT CODE OR STANDARD |
| | USED TO ESTABLISH THE VENTILATION REQUIREMENTS AND |
| | PRESSURE RELATIONSHIPS SHOWN IN THE AIR SUMMARY TABLE. |
| | |
| | 2) M2.1, M2.2, & M3.1: PLEASE LABEL THE DRESSING ROOMS |
| | T140A & T140B ON THE PLANS. PLEASE NOTE THAT EXHAUST |
| | VENTILATION SYSTEMS ARE REQUIRED FOR THE DRESSING ROOMS |
| | AND LOCKER ROOM PER TABLE 403.3 FBC-14. |
| | |
| | 3) M3.1: PLEASE CLARIFY WHY EXHAUST VENTILATION IS |
| | PROVIDED FOR X-RAY ROOMS 2 & 3 BUT NOT FOR X-RAY 1, AND |
| | THE SAME FOR WAITING ROOM T1070 BUT NOT FOR ANY OF THE |
| | OTHER WAITING ROOMS. |
| | |
| | 4) PROVIDE A SUBMITTAL FOR THE NEW DUCT INSULATION WITH |
| | APPROVAL SIGNATURE BY THE DEWIGN PROFESSIONAL OF |
| | RECORD. THE PRODUCT DATA SHALL INDICATE THE MATERIAL IS |
| | LISTED AND LABELED AS HAVING A FLAME SPREAD OF NOT MORE |
| | THAN 25 AND SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 |
| | WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723- |
| | SECTION 602.2.1 MATERIALS WITHIN PLENUMS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |