2017-11-18 12:17:411ST REVIEW FBC-2014 MECHANICAL CODE, GUIDELINES FOR
 DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES-2010
 PERMIT #17101162
 11/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.1: PROVIDE THE CURRENT CODE OR STANDARD
 USED TO ESTABLISH THE VENTILATION REQUIREMENTS AND
 PRESSURE RELATIONSHIPS SHOWN IN THE AIR SUMMARY TABLE.
  
 2) M2.1, M2.2, & M3.1: PLEASE LABEL THE DRESSING ROOMS
 T140A & T140B ON THE PLANS. PLEASE NOTE THAT EXHAUST
 VENTILATION SYSTEMS ARE REQUIRED FOR THE DRESSING ROOMS
 AND LOCKER ROOM PER TABLE 403.3 FBC-14.
  
 3) M3.1: PLEASE CLARIFY WHY EXHAUST VENTILATION IS
 PROVIDED FOR X-RAY ROOMS 2 & 3 BUT NOT FOR X-RAY 1, AND
 THE SAME FOR WAITING ROOM T1070 BUT NOT FOR ANY OF THE
 OTHER WAITING ROOMS.
  
 4) PROVIDE A SUBMITTAL FOR THE NEW DUCT INSULATION WITH
 APPROVAL SIGNATURE BY THE DEWIGN PROFESSIONAL OF
 RECORD. THE PRODUCT DATA SHALL INDICATE THE MATERIAL IS
 LISTED AND LABELED AS HAVING A FLAME SPREAD OF NOT MORE
 THAN 25 AND SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723-
 SECTION 602.2.1 MATERIALS WITHIN PLENUMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  