Plan Review Notes
Plan Review Notes For Permit 17101162
Permit Number 17101162
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-04 10:09:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ON SHEET E2.1, THERE IS A BLOCK NOTE REFERENCING THE
 2017 FBC ENERGY CONSERVATION. THIS PERMIT APPLICATION
 WAS SUBMITTED PRIOR TO THE EFFECTIVE DATE OF THAT CODE
 AND THAT CODE WILL NOT BE USED FOR THIS PROJECT.
 THEREFORE, PROVIDE DETAILS OF ALL EXISTING LIGHTING
 CONTROLS. PROVIDE THE ADDITIONAL LIGHTING CONTROLS
 STIPULATED IN THE ENERGY CONSERVATION CODE. IF NOT TO
 CURRENT CODE, SHOW AS NEW INSTALLATIONS. FBC EC
 405.2.2; FBC 2014 PREFACE.
 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC EC 405.5
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 5. THERE IS NO POWER PLAN INCLUDED IN THIS PLAN. THE
 SCOPE OF WORK STATES THAT WORK WILL BE COMPLETED ON
 WALLS THAT ARE DAMAGED, BUT DOES NOT EXPLAIN ANY
 ELECTRICAL IN THESE WALLS TO BE REPAIRED. PROVIDE
 DETAILS OF ANY ELECTRICAL IN WALLS TO BE REPAIRED,
 NOTING COMPLIANCE WITH NEC 517.13 WHERE APPLICABLE. FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved